This page has specific information related to OmronCIP Communication Driver. For a generic explanation of Device Module, Channels, Nodes, and Points configuration, please refer to the reference guide.

On this page:


Summary

Communication Driver Information
Driver name

OmronCIP 

Implementation DLL 

T.ProtocolDriver.OmronCIP.dll

PLC types supported 

NX-Series (tested with NX102-9020) 

ManufacturerOMRON
Protocol

OmronCIP (CIP over TCP/IP)

Interface

TCP/IP

PC Requirements

Ethernet board 


Channels Configuration

Protocol Options

Model: Set the PLC model.

It can be: 

NX-Series: For all models NX-Series and compatible


Nodes Configuration

Station Configuration

Stations syntax: <IP > ; <Port > ; <Slot> 

Where: 

<IP> = IP address of the slave device in the network 

< Port > = TCP port where the slave device is listening (default is 44818) 

<Slot> = Slot is the Slot number where the CPU is connected. 

Example Nodes Configuration

NameNodePrimaryStationSecundaryStationDescription
Node1OmronCIP192.168.1.101;44818;0


Points Configuration

Address Column Configuration

The syntax for the ControlLogix communication points are: 

<Type> : <DeviceTagName> 


Type: Type is the data type of the Tag in PLC. 

The valid type values are:

TypeReadWriteSize

BOOL 

YesYes

1 bit 

SINT 

YesYes

1 byte or 8 bits 

INT 

YesYes

2 bytes or 16 bits 

DINT 

YesYes

4 bytes or 32 bits 

REAL 

YesYes

4 bytes or 32 bits IEEE Floating point 

LREAL 

YesYes

8 bytes or 64 bits IEEE Floating point 

STRING 

YesYes

n bytes 


DeviceTagName: Tag Name in PLC.


Troubleshoot

The status of the driver execution can be observed through the diagnostic tools, which are: 

  • TraceWindow (with Settings, Device enabled)
  • PropertyWatch 
  • ModuleInformation

The status value of 0 (zero) means communication success. Negative values indicate internal driver error and positive values mean protocol error. 


Error Codes

ErrorCodeDescriptionPossibleSolution

Success 

None

-100 

Error Sending Message 

  • Turn PLC on 
  • Plug the PLC Ethernet cable 
  • Check configured IP Address field in Device > Node
  • Ping PLC using prompt command 

-101 

Error Sending and Waiting Message 

-102 … -105 

Error creating TCP/IP connection 

-106 

Error Receiving Message 

-112 

Timeout Start Message 

  • Turn PLC on
  • Plug the PLC Ethernet cable
  • Ping PLC using prompt command
  • Check configured IP Address field in Device > Node
  • Increase the driver timeout field in Device > Channel

-113 

Timeout between Treated Chars 

-114 

Timeout End Message 

-115 

Timeout Connect 

-200 

Protocol Error 

  • Check if the PLC model is compatible with driver documentation 
  • Check the configured Address field in Device > Points

-201 

Invalid Protocol 

  • Check if the PLC model is compatible with driver documentation 
  • Contact technical support

-202 

Invalid Station 

  • Check configured IP Address field in Device > Node
  • Restart the driver

-204 

Invalid Message Sequence 

  • Check if the PLC model is compatible with driver documentation
  • Check the configured Address field in Device > Points 

> 0 

CIP Error 

See CIP error codes table


CIP Error Codes

The following error codes are in decimal. 

Error CodeDescription

Connection Failure. 

Insufficient resources. 

Value invalid. 

IOI could not be deciphered or tag does not exist. 

Unknown destination. 

Data requested would not fit in response packet. 

Loss of connection. 

Unsupported service. 

Error in data segment or invalid attribute value. 

10 

Attribute list error. 

11 

State already exists. 

12 

Object model conflict. 

13 

Object already exists. 

14 

Attribute not settable. 

15 

Permission denied. 

16 

Device state conflict. 

17 

Reply will not fit. 

18 

Fragment primitive. 

19 

Insufficient command data / parameters specified to execute service. 

20 

Attribute not supported. 

21 

Too much data specified. 

26 

Bridge request too large. 

27 

Bridge response too large. 

28 

Attribute list shortage. 

29 

Invalid attribute list. 

30 

Embedded service error. 

31 

Failure during connection. 

34 

Invalid reply received. 

37 

Key segment error. 

38 

Number of IOI words specified does not match IOI word count. 

39 

Unexpected attribute in list. 

In this driver is very important to enable the TraceWindow messages, as invalid addresses can cause all the communication block with the PLC to fail, the TraceWindow tool (when Device is enabled on the settings) will display the first invalid address found on the block. 

In order to have a quick view on the many communication blocks, open the ModuleInformation, navigate on the tree to find OmronCIP and them select the Read Groups. Looking at the number and success and fail communication counters, you can easily identify if there is a block with error and then use the TraceWindow to locate the wrong address.



Solution OmronCIP Driver -200 Fault

Using the OmronCIP driver to communicate with an Omron NX-102 PLC.

Decrease the value of your MaxSimultaneousConnections property, if it's settet as 5, you can try decrease to 4 or 3. Besides that, you can try to decrease value of NodeConnections too. These properties can be found in Edit > Devices > Channels > Settings, like the image bellow:


Add value 3 to retry property, in Edit > Devices > Channels > Timeout, like the image bellow: