This document has only the specific information about the device connection settings and its address syntax.
Refer to the User Guide for more information on the Device Module.
Summary
MelsecFX communication driver implements communication with Mitsubishi FX Series PLCs using Melsec Q 1E frame. It operates as a Master on TCP/IP networks. The communication blocks are dynamically created according to the pooling cycle defined on the AccessType for each point.
Communication Driver Information | |
---|---|
Driver name | MelsecFX |
Assembly Name | T.ProtocolDriver.MelsecFX |
Assembly Version | 1.0 |
Available for Linux | False |
Devices supported | Mitsubishi FX Series PLCs and compatibles (MelsecQ 1E Frame) |
Manufacturer | Mitsubishi |
Protocol | Melsec Q 1E frame |
Interface | TCP/IP |
Multi-threading | User defined |
Max number of nodes | User defined |
PC Requirements | Ethernet port |
Supported Operands
Operand | Read | Write | Data Type | Address size |
---|---|---|---|---|
D - Data register | Yes | Yes | Short | 2 bytes |
W - Link register | Yes | Yes | Short | 2 bytes |
R - File register | Yes | Yes | Short | 2 bytes |
TN – Timer Current value | Yes | Yes | Short | 2 bytes |
TS – Timer Contact | Yes | Yes | Bit | 1 bit |
TC – Timer Coil | Yes | Yes | Bit | 1 bit |
CN – Counter Current value | Yes | Yes | Short | 2 bytes |
CS – Counter Contact | Yes | Yes | Bit | 1 bit |
CC – Counter Coil | Yes | Yes | Bit | 1 bit |
X - Input relay | Yes | Yes | Bit | 1 bit |
Y - Output relay | Yes | Yes | Bit | 1 bit |
M - Internal relay | Yes | Yes | Bit | 1 bit |
B - Link relay | Yes | Yes | Bit | 1 bit |
F - Annunciator | Yes | Yes | Bit | 1 bit |
Channels Configuration
Protocol Options
- Maximum size of blocks: Defines the maximum of addresses in a read block.
Settings
TCP/IP:
- NodeConnections: Defines the maximum number of parallel requests that will be sent to each node (asynchronous communication)
Nodes Configuration
Station Configuration
TCP/IP:
- Station syntax: <IP address> ; <Port number>
Where :
- <IP address>: IP address of the slave device in the modbus network
- <Port number>: TCP port where the slave device is listening (default is 44818)
E.g.: 192.168.1.1 ; 5551
Points Configuration
The syntax for the MelsecFX communication points is: <Operand> <Address>
Where :
- <Operand>: Represents the Device Memory :
- <Address>: Address number
Operand |
---|
D - Data register |
W - Link register |
R - File register |
TN – Timer Current value |
TS – Timer Contact |
TC – Timer Coil |
CN – Counter Current value |
CS – Counter Contact |
CC – Counter Coil |
X - Input relay |
Y - Output relay |
M - Internal relay |
B - Link relay |
F - Annunciator |
Driver Revision History
MelsecFX Revision History | |
---|---|
Version | Notes |
1.0 | Initial release on new documentation standards. |