This document has only the specific information about the device connection settings and its address syntax.
Refer to the User Guide for more information on the Device Module.
Summary
Communication Driver Information | |
---|---|
Driver name | Facon |
Assembly Name | T.ProtocolDriver.Facon |
Assembly Version | 1.0 |
Available for Linux | False |
Devices supported | Devices using Facon Protocol |
Manufacturer | FATEK AUTOMATION |
Protocol | FACON-PLC Communication Protocol |
Interface | Serial or TCPIP |
PC Requirements | Ethernet port |
Channels Configuration
Protocol Options
The channel configuration options are system standard as described on the platform reference guide.
Node Configuration
Station Configuration
- DeviceID: The PLC Station Number. The valid values are 0 to 254, where 0 means the message is for all slave stations
For TCP/IP only:
- IP: IP address of PLC
- Port: IP Port used in the PLC. Default value: 500
Point Configuration
Address
The syntax for the Facon communication points is: <Operand><Address>
- <Operand>: Indicates the memory area. The valid values are:
Operand | Read | Write | Bit Read | Bit Write | Data Type | Address size |
X Input discrete | Yes | Yes | Yes | Yes | Byte | 1 byte |
Y Output relay | Yes | Yes | Yes | Yes | Byte | 1 byte |
M Internal relay | Yes | Yes | Yes | Yes | Byte | 1 byte |
S Step relay | Yes | Yes | Yes | Yes | Byte | 1 byte |
T Timer discrete | Yes | Yes | Yes | Yes | Byte | 1 byte |
C Counter discrete | Yes | Yes | Yes | Yes | Byte | 1 byte |
TMR Timer register | Yes | Yes | Yes | Yes | Word | 2 bytes |
CTR Counter register | Yes | Yes | Yes | Yes | Word | 2 bytes |
HR Data register | Yes | Yes | Yes | Yes | Word | 2 bytes |
DR Data register | Yes | Yes | Yes | Yes | Word | 2 bytes |
- <Address>: Indicates the data address in the memory area.
E.g.: M0 (Operand = M, Address = 0)
TIP
Driver Revision History
Facon Revision History | |
---|---|
Version | Notes |
1.0 | Initial release on new documentation standards. |