The MelsecFX communication driver implements communication with Mitsubishi FX Series PLCs using Melsec Q 1E frame. It operates as a Master on TCP/IP networks. The communication blocks are dynamically created according to the pooling cycle defined on the AccessType for each point.

Summary Information

Communication Driver Name: MelsecFX

Implementation DLL: T.ProtocolDriver. MelsecFX.dll

Protocol: Melsec Q 1E frame

Interface: TCP/IP 

PLC types supported: Mitsubishi FX Series PLCs and compatibles

Multi-threading: User defined

Max number of nodes: User defined

PC Hardware requirements: Standard PC Ethernet interface board

Supported Operands:


OperandRead WriteData TypeAddress Size
D - Data registerYesYesShort2 bytes
W - Link registerYesYesShort2 bytes
R - File registerYesYesShort2 bytes
TN – Timer Current valueYesYesShort2 bytes
TS – Timer ContactYesYesBit1 bit
TC – Timer CoilYesYesBit1 bit
CN – Counter Current valueYesYesShort2 bytes
CS – Counter ContactYesYesBit1 bit
CC – Counter CoilYesYesBit1 bit
X - Input relayYesYesBit1 bit
Y - Output relayYesYesBit1 bit
M - Internal relayYesYesBit1 bit
B - Link relayYesYesBit1 bit
F - AnnunciatorYesYesBit1 bit



Channel Configuration

Protocol Options

Maximum size of blocks: Defines the maximum number of addresses in a read block

Settings

TCP/IP:

NodeConnections: Defines the maximum number of parallel requests that will be sent to each node (asynchronous communication)



Node Configuration

Station Configuration

TCP/IP:

Station syntax: <IP address>;<Port number>

Where:

    • <IP address> = The IP address of the slave device in the Modbus network
    • <Port number> = The TCP port where the slave device is listening (default is 44818)

Ex: 192.168.1.1 ; 5551



Point Configuration

The syntax for the MelsecFX communication points is: <Operand><Address>

  • D Data register
  • W Link register
  • R File register
  • TN Timer Current value
  • TS Timer Contact
  • TC Timer Coil
  • CN Counter Current value
  • CS Counter Contact
  • CC Counter Coil
  • X Input relay
  • Y Output relay
  • M Internal relay
  • B Link relay
  • F Annunciator

Where:

  • <Operand> = Represents the Device Memory
  • <Address> = Address number



Troubleshoot

The status of the driver's execution can be observed through the diagnostic tools, which are:

• Trace window
• Property Watch
• Module Information

The above tools indicate if the operations have succeeded or have failed. A status of 0 (zero) means communication is successful. Negative values indicate internal driver errors, and positive values indicate protocol error codes.