Summary Information

Communication Driver Name: Facon

Implementation DLL: T.ProtocolDriver. Facon.dll

Protocol: FACON-PLC Communication Protocol

Interface: Serial or TCPIP

PLC types supported: Devices using the Facon Protocol

Manufacturer: FATEK AUTOMATION

PC Hardware requirements: COM Port or Ethernet board



Channel Configuration

Protocol Options

The channel configuration options are system standard



Node Configuration

Station Configuration

DeviceID: The PLC Station Number. The valid values are 0 to 254, where 0 means the message is for all slave stations

For TCP/IP only:

  • IP =  The IP address of PLC
  • Port = The IP Port used in the PLC. Default value: 500



Point Configuration

Address

The syntax for the Facon communication points is: <Operand><Address>

Where:

  • Operand: Indicates the memory area. The valid values are:
OperandRead WriteBit ReadBit WriteData TypesAddress Size
X Input discreteYesYesYesYesByte1 byte
Y Output relayYesYesYesYesByte1 byte
M Internal relayYesYesYesYesByte1 byte
S Step relayYesYesYesYesByte1 byte
T Timer discreteYesYesYesYesByte1 byte
C Counter discreteYesYesYesYesByte1 byte
TMR Timer registerYesYesYesYesWord2 bytes
CTR Counter registerYesYesYesYesWord2 bytes
HR Data registerYesYesYesYesWord2 bytes
DR Data registerYesYesYesYesWord2 bytes
  • Address: Indicates the data address in the memory area

Ex: M0 (Operand = M, Address = 0)

For bit read/write, use the Bit field in the Modifiers column under Edit > Devices > Points



Troubleshoot

The status of the driver's execution can be observed through the diagnostic tools, which are:

• Trace window
• Property Watch
• Module Information

The above tools indicate if the operations have succeeded or have failed. A status of 0 (zero) means communication is successful. Negative values indicate internal driver errors, and positive values indicate protocol error codes according to the Facon specification.