Summary Information

Communication Driver Name: DHRIO

Implementation DLL: T.ProtocolDriver.DHRIO.dll

Protocol: DH+ network

Interface: TCPIP

PLC Types Supported: PLC5 or SLC500 devices using 1756-DHRIO (ControlLogix DHRIO Communication Module) in ControlLogix PLC

Manufacturer: Rockwell

PC Hardware Requirements: Ethernet board



Channel Configuration

Protocol Options

Model: Select the PLC Model: 5 or 500



Node Configuration

Station Configuration

Station syntax: <IP>;<Port>;<BackPlane>;<DHRIO Slot>;<DHRIO Channel>;<DH+Node>

Where :

  • <IP> = The IP address of the ControlLogix device in the network
  • <Port> = The TCP port where the ControlLogix device is listening (default is 44818)
  • <BackPlane> = Used in the device
  • <DHRIO Slot> = The slot used for the 1756-DHRIO module in ControlLogix
  • <DHRIO Channel> = The channel used for the 1756-DHRIO module in ControlLogix
  • <DH+Node> = The node used in the DH+ network

Station Example

The PrimaryStation is: 192.168.1.101 ; 44818 ; 1 ; 2 ; A ; 0



Point Configuration

Address

The syntax for the AB Ethernet communication points is: <FileType><FileNumber>:<Address>[Parameter]

  • FileType: the valid values are:
TermRead WriteBit ReadBit WriteData TypeAddress Size
N IntegerYesYesYesYesWord2 bytes
B BinaryYesYesYesYesWord2 bytes
F FloatPointYesYesYesYesSingle4 bytes
O OutputLogicalYesYesYesYesWord2 bytes
I InputLogicalYes
Yes
Word2 bytes
S StatusYesYesYes
Word2 bytes
T Timer (Model 500 only)YesYes

Word or Bit2 bytes or 1 bit
R Control (Model 500 only)YesYes

Word or Bit2 bytes or 1 bit
C Counter (Model 500 only)YesYes

Word or Bit2 bytes or 1 bit
  • FileNumber: The File number related to the FileType
  • Address: The Element address in the configured File
  • Parameter: Additional parameter for the Timer, Control, and Counter

Ex.: .Len, .Pre, .ACC, .EN, .TT, .DN, etc.

Address Example

Address= N7:10



Troubleshoot

The status of the driver's execution can be observed through the diagnostic tools, which are:

• Trace window
• Property Watch
• Module Information

The above tools indicate if the operations have succeeded or have failed. A status of 0 (zero) means communication is successful. Negative values indicate internal driver errors, and positive values indicate protocol error codes according to AB specification.