This document has only the specific information about the device connection settings and its address syntax.

Refer to the User Guide for more information on the Device Module.



Summary

MelsecFX communication driver implements communication with Mitsubishi FX Series PLCs using Melsec Q 1E frame. It operates as a Master on TCP/IP networks. The communication blocks are dynamically created according to the pooling cycle defined on the AccessType for each point.

Communication Driver Information
Driver nameMelsecFX
Assembly NameT.ProtocolDriver.MelsecFX
Assembly Version1.0
Available for LinuxFalse
Devices supported 

Mitsubishi FX Series PLCs and compatibles (MelsecQ 1E Frame)

ManufacturerMitsubishi
ProtocolMelsec Q 1E frame
InterfaceTCP/IP
Multi-threadingUser defined
Max number of nodesUser defined
PC RequirementsEthernet port

Supported Operands

Operand

Read

Write

Data Type

Address size

D - Data register

Yes

Yes

Short

2 bytes

W - Link register

Yes

Yes

Short

2 bytes

R - File register

Yes

Yes

Short

2 bytes

TN – Timer Current value

Yes

Yes

Short

2 bytes

TS – Timer Contact

Yes

Yes

Bit

1 bit

TC – Timer Coil

Yes

Yes

Bit

1 bit

CN – Counter Current value

Yes

Yes

Short

2 bytes

CS – Counter Contact

Yes

Yes

Bit

1 bit

CC – Counter Coil

Yes

Yes

Bit

1 bit

X - Input relay

Yes

Yes

Bit

1 bit

Y - Output relay

Yes

Yes

Bit

1 bit

M - Internal relay

Yes

Yes

Bit

1 bit

B - Link relay

Yes

Yes

Bit

1 bit

F - Annunciator

Yes

Yes

Bit

1 bit


Channels Configuration

Protocol Options

  • Maximum size of blocks: Defines the maximum of addresses in a read block.

 Settings

TCP/IP:

  • NodeConnections: Defines the maximum number of parallel requests that will be sent to each node (asynchronous communication)



Nodes Configuration

Station Configuration

TCP/IP:

  • Station syntax: <IP address> ; <Port number>

Where :

  • <IP address>: IP address of the slave device in the modbus network
  • <Port number>: TCP port where the slave device is listening (default is 44818)

E.g.: 192.168.1.1 ; 5551



Points Configuration

The syntax for the MelsecFX communication points is: <Operand> <Address>

Where :

  • <Operand>: Represents the Device Memory :
  • <Address>: Address number

Operand

D - Data register

W - Link register

R - File register

TN – Timer Current value

TS – Timer Contact

TC – Timer Coil

CN – Counter Current value

CS – Counter Contact

CC – Counter Coil

X - Input relay

Y - Output relay

M - Internal relay

B - Link relay

F - Annunciator


Driver Revision History

MelsecFX Revision History
Version Notes
1.0Initial release on new documentation standards.