Overview

The AlarmItems represent individual tags or expressions monitored within the solution. The AlarmItem triggers an alarm event when a defined condition occurs, notifying users about it. To define an AlarmItem on your solution, the user must a tag name, the condition that triggers the alarm (e.g., Hi, Lo, Rate of Change), and the threshold value (Limit). The software platform offers optional properties for customization, including priority, auxiliary values, and the alarm message.

On this page: 



AlarmItem Configuration

To configure a new or existing AlarmItem, follow the steps below:

  1. Access Alarms Items.

  2. On the Tag Name column, type the Tag name or select from the available list. Alternatively, copy and paste the Tag's name from Unified Namespace → Tags.

  3. Enter the condition to trigger the alarm in the Condition field and configure the threshold value in the Limit field.
  4. In the Group field, choose which AlarmGroup object that defines the behavior for this AlarmItem.
  5. Once finished, press Enter on your keyboard to save the AlarmItem.


To modify an existing AlarmItem, double-click and modify the desired field. Note that any changes made to the Item will take effect immediately, and the new or modified AlarmItem will be evaluated against the tag values in real-time.


The image below illustrates the process described above. In it, we created an AlarmItem monitoring the tag "ExampleTag" and when its value exceeds or is equal to 50, it will trigger an alarm in the "Warning" AlarmGroup.

For more details about each available property field, see the section below.


Properties Reference

Alarm Item Properties

When configuring an AlarmItem, the essential properties to define are the Tag Name and Condition. These two elements form the core of the configuration, dictating when and how alarms are triggered. Additionally, you can set up other properties based on the specific use of the alarm. The following is a table describing each available property field:

If a property column is not visible on the grid, enable it by right-clicking the grid header and selecting it from the list.

Property

Description

ID

The unique identifier for the item.

VersionID

The version identifier associated with the item.

TagName

The name of the tag being monitored for alarm events.

Condition

Defines the condition that triggers the alarm. The next section of this page describes in more detail the different options for this property.

Limit

Defines the predefined threshold for the alarm.

Limit1

A secondary threshold value. You should use this property in conjunction with the Limits by Shift functionality. Learn more on the Alarm Limits page.

Limit2

A tertiary threshold value. Learn more on the Alarm Limits page.

Disable

Enables or Disables the alarm.

Deadband

Defines a range in which changes are ignored.

Setpoint

The desired target value.

SetpointDeadband

A range around setpoints where changes are ignored.

Group

The group to which the alarm item belongs.

Area

The area designation for alarm management.

Priority

Defines the priority level of the alarm.

AuxValue

It provides additional information about the alarm, such as the responsible team to be associated with an Alarm Area. Read more on the Alarms Areas page.

AuxValue2

A secondary auxiliary value.

AuxValue3

A tertiary auxiliary value.

LockState

The current lock status of the alarm item.

LockOwner

The user or system that locked the item.

DateModified

The date the alarm item was last modified.

DateCreated

The date the alarm item was created.

Comment

The comments or notes related to the alarm item.

Message

This is the alarm message displayed to the user upon triggering the alarm.

Alarm Condition Options

The Condition property defines the trigger for the alarm using the Limit property as the threshold value. It offers a wide range of options and the table below describes them in more detail:

Condition

Description

Hi

Tag >= Limit.

HiHi

Tag >= Limit (when acknowledged, a Hi alarm is automatically acknowledged for the same Tag).

Lo

Tag <= Limit.

LoLo

Tag <= Limit (when acknowledged, a Lo alarm is automatically acknowledged for the same Tag).

RateOfChange

The tag's rate of change >= Limit.

DeviationMinor

Absolute value: (Tag - Setpoint) > Limit.

DeviationMajor

Absolute value: (Tag - Setpoint) > Limit.

Equal

Tag = Limit.

GreaterThan

Tag > Limit.

GreaterEqual

Tag >= Limit.

LessThan

Tag < Limit.

LessEqual

Tag <= Limit.

Changed

Tag value changed.

ChangedUp

Tag value increased.

ChangedDown

Tag value decreased.

NotEqual

Tag different from limit.