Overview

When the solution is running, and the Designer is connected with the runtime, the Alarms Monitor page show basic status of its Alarm Groups, and a refined User Interface using the AlarmViewer controlAlarmGroups, as well as a Alarm Viewer user interface, which allows to monitor online and historical alarms.

On this page: 

Table of Contents
stylenone


Image Added

Monitoring

Alarm Status

Alarms

You can access the monitor by navigating to Alarms → Alarms Monitor.

When the solution is runtime, the monitor will display an AlarmViewer preview, and a table with the runtime properties of the Alarm Groups. a table of properties with real-time information about the alarms module. 

Alarm Viewer 

The Alarm Viewer is an out-of-box User Interface to monitor Alarms. This interface was , created using the same tools available to create displays and the AlarmViewer Control.  When creating displays in your application there is template in AlarmsPage similar to this one embedded in the Designer. 

Tip

Using a Browser, with no installation required, you can verify the Alarm Status of remote server. With the following URL.

http://localhost:3101/html5/?Solution=Monitor&StartupLayout=AlarmViewerAlarms

Locahost: shall be replaced by the IP or Computer Network Name of the computer you want to access. The port 3101 shall reflect the Port the Runtime is using, typically it is 3101 for production profile, and 3201 for Development profile. The reaming for rest of the URL remains the same.


Alarms Monitor Table Columns

The information in this table is constructed from the runtime properties of the object: Alarm.Group.<GroupName>.  

Additionally of showing in the monitor table, the properties can be accessed on Displays or Scripts, using the following syntax

@Alarm.Group.<Name>.<PropertyName>


Alarm Groups Monitor Table

Property

Description

Name

The name of the Alarm Group

Total Count

The overall count of the alarms int that Group

UnAckCount

The count of unacknowledged alarms in the group.

ActiveUnAckCount

The count of active but unacknowledged alarms in the group.

Prioritltem

The message of top priority alarm in the group that is active. 

LastAlarmItemNotified

The most recent alarm item that triggered a notification.



In this section:

Page Tree
root@parent
spacesV10