This document has only the specific information about the device connection settings and its address syntax.
Refer to the User Guide for more information on the Device Module.
Summary
Modbus driver implements communication with PLC and IO devices compatible with Modbus Open Standard protocol. It operates as a Master on TCP/IP or serial networks. The communications blocks are dynamically created according to the pooling cycle defined on the AccessType for each Device Point.
Communication Driver Information | |
---|---|
Driver name | UnityPro |
Assembly Name | T.ProtocolDriver.ControlExpert |
Assembly Version | 1.7.0.0 |
Available for Linux | False |
Devices supported | PLC's Quantum, Momentum M340 and M580 - Schneider-Electric |
Manufacturer | Schneider-Electric |
Protocol | MODBUS RTU, ASCII and TCP |
Interface | TCP/IP and Serial |
PC Requirements | Standard PC Ethernet interface board, RS485 or RS232 port |
Supported Operands:
Operand | Read | Write | Data Type | Address size |
0 – %Q or %M - Coils | Yes | Yes | Bit | 1 bit |
1 – %I - Input Status | Yes | - | Bit | 1 bit |
3 – %IW - Input Registers | Yes | - | Word | 2 bytes |
4 – %MW - Holding Registers | Yes | Yes | Word | 2 bytes |
Channels Configuration
Protocol Options
BlockSize: Defines the maximum amount of items per group, the default value is 250.
If the communication points are configured in sequence and the BlockSize equals 250, the driver can create the internal groups with 125 Registers or 2000 Coils.
Encoding: Determines how the information will be packed into the message fields and decoded. The options are:
- RTU: Remote Terminal Unit mode, where each 8–bit byte in a message contains two 4–bit hexadecimal characters.
- ASCII: The message is encoded in ASCII mode, where each 8–bit byte in a message is sent as two ASCII characters.
- RTU TCP: The default transmission mode when the message is carried on a MODBUS TCP/IP network. It contains information to allow the recipient to recognize message boundaries even if the message has been split into multiple packets
- SingleWrite: Indicates the driver behavior for the writings with only one item:
- Use block write : The driver uses the 0x0F command for Coils, or the 0x10 command for Holding Registers
- Use single write: The driver uses the 0x05 command for Coils, or the 0x06 command for Holding Registers
Settings
Serial and MultiSerial channels:
- Default configuration for ASCII mode:
- DataBits: 7
- StopBits: 1 if parity is used; 2 if no parity is used
- Default configuration for RTU mode:
- DataBits: 8
- StopBits: 1 if parity is used; 2 if no parity is used
Set the other fields according to your Serial or MultiSerial port configuration
TCP/IP channels:
- NodeConnections: Defines the maximum number of parallel requests that will be sent to each node (asynchronous communication)
Nodes Configuration
Station Configuration
- SlaveId: Set this field with the address of the slave device in the network. They can be addressed from 1 to 247 for serial nodes, or 0 to 255 for TCP/IP nodes. The address 0 is used for the broadcast.
Serial channels:
- Station syntax: <SlaveId>
E.g.: 1
MultiSerial channels:
- Station syntax: <Com Port> ; <SlaveId>
Where:
- <Com Port>: the serial port number
E.g.: com1 ; 1
TCP/IP channels:
- Station syntax: <IP address> ; <Port number> ; <SlaveId>
Where :
- <IP address>: IP address of the slave device in the modbus network
- <Port number>: TCP port where the slave device is listening (default is 502)
E.g.: 192.168.1.101 ; 502 ; 1
Points Configuration
The syntax for the UnityPro communication points is: <Operand><Address>
Where:
- <Operand>: indicates the memory area, the valid values are:
Operand |
---|
0 – %Q or %M - Coils |
1 – %I - Input Status |
3 – %IW - Input Registers |
4 – %MW - Holding Registers |
For more information about the valid operands, see the Supported Operands table aforementioned.
- <Address>: indicates the data address in the memory area, from 1 to 65535
E.g.: 400001 (Operand = 4 (%MW), Address = 1)
Troubleshoot
Modbus protocol error codes | ||
---|---|---|
Error | Name | Description |
1 | ILLEGAL FUNCTION | The function code received in the query is not allowable. |
2 | ILLEGAL DATA ADDRESS | The data address received in the query is not allowable. |
3 | ILLEGAL DATA VALUE | A value contained in the query data field is not allowable. |
4 | SLAVE DEVICE FAILURE | Error while attempting to perform the requested action. |
5 | ACKNOWLEDGE | Request accepted, but a long duration of time will be required. |
6 | SLAVE DEVICE BUSY | The slave is engaged in a long–duration program command. |
7 | NEGATIVE ACKNOWLEDGE | Cannot perform the program function received in the query. |
8 | MEMORY PARITY ERROR | Parity error in the extended memory. |
Driver Revision History
UnityPro Revision History | |
---|---|
Version | Notes |
1.7.0.0 | Initial release on new documentation standards. |