Overview

The Runtime Startup section of the Designer Interface allows you to start and stop the execution of the solution, specify the execution profile you want to use, and customize all connection settings for that execution.

The settings defined here are also applied when the startup is executed via the Start Solution command line or when starting the solution as a Windows service. This section focuses on the various settings when using the Designer configuration tool. For advanced information to run solutions in production environments, refer to the page Solution Deployment.

On this page:


Runtime Startup Settings

Runtime Startup Page, when Basic Modules Filter is Selected.

Runtime Startup Page when All Features are enabled. 

Target Platform

Some specific configurations, including Windows Authentication and Windows Service, are exclusively available when Windows is selected as the Target Platform for the solution.

This option unlocks the specific functionalities and security feature that are inherent and exclusive to Windows operational systems.

Settings on this page define which profile the solution will use, communication ports, and other configurations. They allow control over starting and stopping the execution, as well as managing the online configuration.

Main Commands and Options

Run Startup

This command button starts the application.

Stop

This command button stops the application.

Online configuration

You can use Enable Online Configuration to apply changes in real-time. All changes must be saved before they can appear on a screen.

This is a setting you check to make changes apply immediately. You need to be connected to the running app for it to work.


Execution Profiles

Execution Profiles allow for the dynamic replacement of database connections or device nodes during solution runtime, enabling smooth transitions between development, validation, and production environments.

The solution uses its main configuration in the Production profile without additional overrides. When you change from the Production Profile to any other profile in Runtime → Startup, this change will be reflected in the Startup Command line.

Execution Profiles


Development

Provides an environment with debugging and development tools enabled. Developers use this profile during the development and testing phases to test and troubleshoot the solution.

Production

Optimizes performance and stability for running in a production environment. Based on the selected profile, it automatically applies different database connections and device configurations.

The User can enable Validation and Custom profiles on Runtime / Execution Profiles. For detailed information, refer to the Runtime Execution Profiles.


Startup Port Settings

The startup port settings allow you to define the network ports used by the application, both for internal communication and external access via the web. You can activate automatic port allocation and configure authentication via Windows.

Startup Port Settings

The ports must be enabled and available on the server.

Main Port

Sets the port that each execution profile uses to access. By default, the Development profile uses the 3301 port, the Validation execution profile uses the 3201 port and the Production execution profile uses the 3101 port. These ports must be enabled and available on the server.

Auto Ports

Ensures that the software runs even when the specified main ports are unavailable. When enabled, and if the port defined as the Main Port is unavailable, the software will automatically search for and select an available port to use.

WA Port

Defines the port used by software platform for access with Windows Authentication.

Windows Authentication

Checks if the system can only accept Windows Authentication.

Web Port

Enables the web port in the solution. By default, the port is set to 80.

Windows Service

Configures the solution to run as a Windows Service. When enabled, the application will start automatically with Windows, running in the background without requiring user login. Use the “Apply Service” button to install the service and the “Remove Service” button to uninstall it.


Execution Environment

The execution environment allows you to choose between running the application locally or on a solution server. This section also includes settings for the MQTT broker, facilitating communication between IoT devices.

Execution Environment

Local Computer

The Solution is launched locally on the local computer.

Solution Server

Read-only. Displays the IP address or the name of the computer where the solution is, which is based on the configuration in the Server tab.

Path/Use Solution Path

Overrides the default execution path, which is the solution file location.

Used by the system to allow one station to automatically update the solution in the redundant pair when doing online solution changes and HotStart commands. 


Startup Modules

Startup Modules allow you to define which application components will be active at startup, ensuring that only the necessary modules are loaded, thus optimizing resources and performance.

Startup Modules

Select which modules will be started up when running the solution.

Devices

Enables Devices module.

Alarms

Enables Alarms module.

Historian

Enables Historian module.

Datasets

Enables Datasets module.

Reports

Enables Reports module.

Scripts

Enables Scripts module.

Displays

Enables Displays module.

OPC Server

Enables the OPC Server.



Redundancy Enabled

Redundancy configurations allow you to define a high-availability environment, where a secondary server can take over operations in the event of a primary server failure.

Redundancy Enabled

Primary Server IP/Port

Enter the IP address and port of the primary server.

Secondary Server IP/Port

Enter the IP address and port of the secondary server.

Timeout

Connection timeout time in seconds. If reached, this will cause the system to switch to the secondary server. 

On Primary Startup

Switch back to primary: When the primary instance becomes available again after a failure, the system will automatically switch back to using the primary instance.

Keep secondary active: Even after the primary instance is restored, the system continues to use the secondary instance until manually switched back.

Replication

AlarmHistorian: Replicates alarm history data to ensure that alarm events are preserved and accessible even if the primary instance fails.

TagHistorian: Replicates tag history data, which includes historical values of tags, ensuring data continuity and availability.



Command Lines and URLs

The command lines and launch URLs provide the commands and shortcuts necessary to launch the application and access different clients, such as RichClient, SmartClient, and HTML5 Client, ensuring flexibility in accessing the application.

Click the button to start the Client.

Command Lines and URLs

Startup Command line

TStartup.exe: It's the executable file responsible for initiating the startup process.

/solution: Specifies the path to the solution file that will be run.

/profile: Defines the Execution Profile to be used. Refer to Execution Profiles for more details.

/profile:1 refers to the Development Execution Profile;

/profile:2 refers to the Validation Execution Profile;

/profile:3 refers to the Custom Execution Profile.

/OnlineConfig:true: Indicates whether the online configuration is enabled or not.

/wa: Enables the Windows Authenticator.

/port1:3301: Specifies the port number used during the startup.

Rich Client command

TRichClient.exe: It's the executable file used to start the Rich Client.

/port1:3301: Specifies the port number to be used by the Rich Client.

Smart Client URL

This URL is used to access the Smart Client interface via a web browser, allowing for interaction with the industrial solution using advanced, intelligent features. The IP address and port number define the network location of the service.

HTML5 Client URL

This URL provides access to the HTML5 Client interface. This allows users to interact with the solution using web technologies and ensures compatibility with modern web browsers.

NoSplash

When checked, suppresses the display of the splash screen during the startup of the application, potentially reducing the startup time.

WA

When checked, enables the Windows Authenticator for added security during the startup and operation of the solution on Windows operating systems.

SSL

When checked, enables Secure Sockets Layer (SSL) for encrypted and secure communication between the client and the server, protecting data integrity and confidentiality.

ViewOnly

When checked, sets the client to a read-only mode, where the user can view but cannot modify the configurations and data.


Accessing HTML5 Clients on Devices Connected to the Same Network

To access HTML5 clients from other devices on the same network, follow these instruction:

Understanding the Localhost Address

  1. The address 127.0.0.1 is the loopback address or "localhost". It refers to the device where the application runs, such as the engineering workstation or the controller computer.

Network Configuration

  1. Assume you have an engineering workstation where your solution runs. This workstation has a specific IP address on the local network, different from 127.0.0.1.

Accessing from Other Devices

  1. Open any browser on the target device (notebook, smartphone).

  2. Enter the IP address of the engineering workstation followed by the port used by the application. The URL format will be http://<Workstation-IP>:<Port>.

Practical Example

Identifying the Workstation's IP Address:

Assume the engineering workstation's IP address is 192.168.0.8 and the application uses port 3201.

Accessing the Application:

In the browser on the target device (notebook, smartphone), type the following URL: http://192.168.0.8:3201/HTML5.

If SSL is enabled, use https://192.168.0.8:3201/HTML5.

This process will allow you to access the HTML5 application running on the engineering workstation from any device connected to the same local network.

The software platform allow you monitor the users connected at runtime. For detailed information, refer to the Security RuntimeUsers.


In this section: