Overview
The focus of this document is to monitor the total duration of an alarm and the occurrences per alarm. This functionality allows users to have a real-time overview of the alarm system, making it easier to understand alarm behaviors and patterns. With this information at hand, operators and system administrators can optimize system functionality and mitigate potential issuesWhen preparing a report or viewing the alarm history, it is important to highlight certain features. One key feature is the duration of past alarms recorded in the system. This document explains the procedure for configuring this aspect.
On this page:
Table of Contents maxLevel 3 style none
Alarm Duration
and OccurrencesDuration is defined only for alarms that require user acknowledgment (ACK), measuring the time from trigger to ACK. The following model presents a step-by-step method on how to obtain the total duration of an alarm and occurrences per alarm.
This method By default, into the SQL tables that register the alarm events there is a column called "Duration", since the data shown in the AlarmWindow comes from this database, viewing the duration of alarms is based on how to display this information in the AlarmWindow AlarmViewer Control or in a separate data grid, then is necessary so this procedure requires some historical alarm data in which there was an ACK from the user.
To obtain the duration of an alarm and other related information, configure the AlarmWindow with your existing alarms to show the Historical values in the project .You can leave the and set Duration column visible in the AlarmWindow configuration to display the alarm duration at runtime, as shown in the image below.
In the context of optimizing a system's productive time, it's about reducing failures. This method can be used to display an example of the top 10 (or 20) historical failures in a system, once according to the duration and once according to frequency.
You can sort the Alarms using the Duration column, or you can filter in a button using the syntax: Duration > xxx.
As in the example below.
To count how often an alarm occurs:
We have a solution for this by setting the AlarmWindow as shown below.
to visible by double click AlarmViewer and follow the steps below.
Step 1 - Set the List comboBox to AlarmHistory.
Step 2 - At Columns, select Duration and check the Visible checkbox at the bottom right.
Number of Occurrences
You can group alarms listed in an AlarmViewer to get an idea of how many times the alarm has gone off.
To achieve this, the AlarmViewer component features a drag-and-drop column functionality, which is, by default, disabled. However, it is possible to enable it by double-clicking the AlarmViewer, then checking the Show Header checkbox. This will activate the option only during runtime.
To utilize it, select the column TagName, drag it to the new area in the AlarmViewer's Then you go in Runtime and drag the "TagName" column to "Drag columns titles here to group data" option, as following example.
The result will be like this, and you can see the count:
To show the duration of all individual alarms as a sum:
An example would be sorting the TagNames by the number of items to find the alarms that occur most often, to see which generates more "beeps" or micro-stops.
It is possible to show the duration of all individual alarms through a query. Here is the code below:
Code Block |
---|
//
@Dataset.Query.Query1.SqlStatement = "SELECT COUNT(TagName) como AlarmCount, TagName, SUM(Duration/10000000) como DurationSum FROM Alarms GROUP BY TagName ORDER BY COUNT(TagName);";
@Tag.Table1 = @Dataset.Query.Query1.SelectCommand();
?// |