Overview

External TagProviders enable direct interaction with variables in remote systems, bypassing the need to create specific tags in the solution. They establish connections with tag sources, which can be set up in a table or directly in the assets, enhancing the versatility of data access and exploration within the Unified Namespace.

Image Added

On this page:

Table of Contents
maxLevel3
stylenone


Understanding

External TagProviders

TagProvider Connections

The External TagProviders refer to the tool which allows to access Communication Device Data Model from any place inside the Solution Designer without creating solution Tags. Data from External Tag Providers can be used in displays, alarms, historian storage, and as communication points, allowing integration of external device data within the solution. It can also be incorporated into the Asset Modeling structure for organization. The External TagProviders feature allows you to access Data Models definitions from external systems, using those variables and structures in any of the platform's modules directly, without having to create any local definition of Tags inside your solution.

Supported TagProviders 

This feature is available for

Children Display
styleh3
excerptTyperich content

Configuring the External TagProviders

All TagProviders have common configuration items: Provider, Access Mode, Name, Description, and Test. The Provider specifies the platform the TagProvider will interface with. Access Mode determines permissions for tag interaction: Read allows data reading, Write permits data writing, and ReadWrite enables both. The Name is a user-defined identifier for the TagProvider instance, aiding in identifying the specific configuration within the software platform. The Description explains the TagProvider's purpose or the platform it interfaces with, providing context for its usage. The Test button verifies the connection settings to ensure successful communication with the specified device or data source.

While some parameters address common needs like connection settings and data access modes, others are unique in that they cater to each system's particular functionalities and technical characteristics. Each External TagProvider has its own configuration parameters tailored to meet specific technical requirements and specifications. These unique parameters ensure that each TagProvider can interface with the platform, enabling data integration according to individual operational requirements.

TagProviders allow connections with external systems to read or write data without creating local tags. Displays and other modules can directly access data from remote systems, even if their structure changes dynamically.

Automatic & Tagless Connections:

  • Connect to external data sources and consume their data models in the Unified Namespace.
  • Access all tags and data structures automatically with simple configuration.
  • The connected provider’s tags and data models are available for use in various modules (Displays, Scripts, Reports, etc.).
  • Support for various systems: Protocols, Historians, or Devices.
  • Easily plot trend charts and access archived data from external Historians.


Devices vs TagProviders

Some connections can be done through Devices and TagProviders. To define which one works best for your application, you should look at how your data is structured.

Devices handle predefined, static data, ensuring control, security, and advanced metadata management, suitable for applications requiring strict validation like HMI and SCADA systems. These environments often require strict regulatory compliance, such as FDA validation in pharmaceutical production or stringent monitoring in manufacturing plants. Devices provide detailed metadata management, including retentiveness, security settings, and visibility control within the platform.

TagProviders are ideal for applications where where data and device configurations change frequently, necessitating real-time update. That type of connections allows you to manage dynamic data, enabling flexible device addition, ideal for IoT and monitoring applications needing situational awareness, such as smart city infrastructures or home automation systems. For instance, TagProviders can dynamically integrate new environmental sensors in a smart energy grid, providing continuous updates and allowing city managers to respond promptly to changing conditions.


Supported TagProviders

Integration with Communication Protocols

Integration with other Applications

Integration with Historian Systems


Info
titleHistorian TagProviders

When the TagProvider Connection is created for a Historian system, it will have two additional features:

  1. Using the Asset(<AssetPath>) on TrendCharts, it will automatically query the Historian to plot the chart. While the other TagProviders can only read and write current values.
  2. Those TagProviders can use be used on Historian Storage Locations, as a target repository to archive time-series data.



Configuring  TagProviders

Configuration Workflow

  • Identify the TagProvider: Based on the communication protocol

Configuration Workflow

To connect to external data sources to use its data definitions models, follow the steps below:

Step 1: Identify the appropriate External TagProviders based on the communication protocol of the external data source
  • (e.g., OPC UA, Modbus
, Custom
  • ).
Step 2: In the software, navigate
  • Create a New Instance: Navigate to the
External
  • TagProviders
configuration
  • section and
create a new ExternalTags Sources instance. Provide necessary information such as the provider's name, communication settings, and any required authentication credentials.

Step 3: Configure the ExternalTags Sources settings to ensure proper communication with the external data source. This may include specifying the IP address, port number, or other communication parameters specific to the data source or protocol.

Step 4: Test the connection between the ExternalTags Sources and the external data source. If the connection is successful, the software will be able to access and process the data from the external source.

Note
titleNote

Once tags are imported using ExternalTags, their organization will reflect the structure provided by the external provider. Direct alterations in the software won't be possible. For any organization or modeling needs, please utilize tools and features available at the source/provider side.

Creating a new ExternalTags Source

In your Engineering Environment, navigate to Unified Namespace → External TagProviders

Click on the 'New Item' button to launch a dialog window titled 'Create New External TagProvider'. From the provided list, select a Communication Protocol and assign an appropriate name.

After you select a Protocol, you will see a configuration table with columns that are similar to the ones in the Channels, Nodes, and Points pages. However, the columns will all be grouped on a single page. For this example, we will use MQTTspB.

The configuration settings are detailed below:

  • Name: Name of the provider. This will be used to access elements from this namespace.
  • Provider: Communication Protocol of choice.
  • Parameters: Char separator for the communication protocol of choice.
  • Primary/Backup Station: Connection String information used to establish a communication (same as on Devices → Nodes).
  • Access: AccessType for this connection (Read/Write/ReadWrite).
  • ReadTime: Read Pooling Rate.
  • WriteTime: Write Rate.

The Primary/Backup Station will be configured according to the communication protocol.

For more information, please refer to the specific protocol documentation.

Working with External TagProviders

Access Elements in Engineering

Once you finish your configuration and establish a successful connection, you will be able to access the variables from the Device in various places within the Engineering Environment.

  • provide necessary information.
  • Test the Connection: Verify and explore the data.
  • Create a New AssetFolder: In the AssetTree, use the toolbar command “Insert Link to TagProvider.”
  • Customize the Alias: For the selected node.


Creating a new TagProvider Connection

Steps:

1.Navigate: Go to Unified Namespace → TagProvider Connections.
2.New Item: Click the ‘New Item’ button to open the ‘Create New TagProvider’ dialog.
3.Select Protocol: Choose a communication protocol and assign a name.
4.Configure: Fill out the configuration table with:

Common Configuration Items:

  • Provider: Specifies the platform the TagProvider will interface with.
  • Access Mode: Determines permissions (Read, Write, ReadWrite).
  • Name: User-defined identifier for the TagProvider instance.
  • Description: Explains the purpose or platform it interfaces with.
  • Test button: Verifies the connection settings.

Unique Configuration Parameters:

Each TagProvider has specific parameters tailored to its functionalities and technical requirements, ensuring proper data integration.

For example, using MQTTspB, the settings will be detailed similarly to Channels, Nodes, and Points.

Image Added


Using TagProviders as Historian Storage Location:

Some TagProviders can be used with the Historian Module to define data storage locations. Typically, TagProviders for historian tools or MQTT can be used as Storage Locations.

By default, the Historian archives data in an SQL Database, but this can be extended with TagProviders.

See Historian Storage Locations for more information


Working with TagProviders

Browsing Values

InUnified Namespace → Asset Tree, after linking a folder to the data from the TagProvider Connection, you can browse the tree. The right-side tables will update, showing the values of the variables in the selected folder.

Image Added

Reading and Writing Values from other Modules 

After including TagProvider in the AssetTree Nodes, you can access that in using the Asset() method.

Browsing the tags

You can start by clicking on the Object Selectionbutton (1). In the left portion of the popup window, you should see a list of objects from every Solution Namespace. Use the name that you defined in the ExternalTags Sources configuration (2) to search for the namespace. 

Expand the list so you can see all the variables from that Device. By selecting an element, you can see the current value read from the Device (3).

Image Removed

Directly accessing tags

You can also access your variables directly through their addresses, following the

.E.g.: If using ControlLogix, the final part of the AssetPath is the address, using

same syntax used in Devices → Points: <ProviderName>.("<Type>:<Address>")

.

E.g.:

  • AssetControlLogix.("/Folder1/DINT:PROGRAM:MAINPROGRAM.MYDINTMyPlcTag")
  • ControlLogix.Asset("/Area1/Line1/DINT:MyArray1DimDINT[0]")

E.g.2:

To read and write the asset with data received from the PLC, you can use the following code with VB.NET:

Image Removed

The tag address can be found under "Edit > Tag > Providers > Browse Values..."

Image Removed

You can also add a Remote Tag to your Display. Go to the Draw Environment, select a TextBox element (or any other component/symbol), and add it to your display. Double-click it and add a TextIO Dynamic with the same method as if you were assigning a tag. 

In the ObjectName field, select the Browse button and search for the desired variables. By doing this, you can display the information from the Communication Protocol directly in you Display, without the need to create a Tag and Communication Point.

The expression field will be filled with the syntax: ?ExternalTags SourcesName?.(”? Address In Provider ?”).

Image Removed

Since the address in the expression is a string, you can assign other Tags or Properties so that it has a Dynamic Configuration.

Image Removed

This feature is not limited to Displays. You can create AlarmItems, store data in Historian Tables, and use this remote variable as a Communication Point to Write Data for a different Protocol.

Image Removed

Using TagProviders on Assets Displays

It is possible to have a full or partial view of the Data Model inside your Solution. On Unified Namespace → Asset Tree, you can create your own Levels and assign a part of the Device's structure to it from the Namespace discussed in the previous section.

This method allows you to import all your model, or just a piece of it, from the selected node down. The name of the Level in the Asset Tree (in Runtime) can be edited in the Description column.

In your Draw Environment, add the AssetControl component, open its configuration, and uncheck the Show only tags check box.

If you have done everything correctly, your Asset View should look something like this in Runtime
Tip

The best way to pickup the right syntax, it is to use the Object Browser Image Added from the top Toolbar, and navigate to the element you need. 

The proper AssetPath is shown on that window as you navigate the tree.


You can use the Asset() syntax, not only in scripts, but on Displays, and in all fields in the software where a Tag is expected, including:

  • On Displays, mapping symbol properties and linking to dynamic properties.
  • On Alarms, creating alarm events.
  • On Historian, archiving the data.

TagProvider Connections Columns

TagProvider Connection Properties

ID

Identifies the TagProvider. 

VersionID

Shows the specific version number.

Name

Names the TagProvider connection for identification and reference.

Protocol

Specifies the communication protocol used for the connection.

ProtocolOptions

Defines additional options for the selected communication protocol.

PrimaryStation

Sets the main station or endpoint for the data source connection.

BackupStation

Specifies a backup station for redundancy in the connection.

FailOverStation

Configures the station to use in case of primary and backup failures.

Interface

Indicates the interface type used.

Settings

Lists the configuration settings for the connection.

Timeout

Sets the maximum time to wait for a response from the remote system.

InitialState

Defines the initial state of the connection when established.

RemoteSettings

Specifies settings for interacting with the remote system.

DriverVersion

Indicates the version of the driver.

Separators

Sets the separators used in the data format.

IsHistorian

Indicates whether the connection involves a historian system.

Access

Specifies the access level required to interact with the connection.

ReadTime

Records the time taken to read data from the remote system.

WriteTime

Records the time taken to write data to the remote system.

ServerIP

Defines the IP address of the remote server.

Level

Classifies the connection within a specific level or hierarchy.

Category

Groups the connection within a specific category for organization.

LockState

Indicates whether the connection settings are locked and cannot be modified.

LockOwner

Identifies the owner responsible for locking the connection settings.

DateCreated

Records the date and time when the connection was created.

DateModified

Records the date and time when the connection was last modified.

Description

Summarizes the purpose and details of the TagProvider connection.



In this section:

Page Tree
root@parent
spacesV10