Download the Solution Example here: AlarmsAreas.dbsln

Name: Logical Alarm Areas

Software Version: 10.1


Summary

This solution example shows demonstrates the many uses of AlarmAreas. Among other things, it is possible to enable, disable, acknowledge, count and filter alarms Alarms based on the Area they are associated with, making it easier to manage large projects.linked to, simplifying the management of complex solutions.

Image Added


Technical Information

To create an AlarmArea, go to Alarms → Areas. It is possible to create SubAreas by

clicking on

selecting an existing AlarmArea and creating a new one inside of it.

Afterwards

Next, go to Alarms → Items, right-click on the column

titles and

headers, enable the Area column,

then edit it to specify which Area

and assign each AlarmItem

belongs

to its corresponding Area by editing the column.
Each AlarmArea has its own alarm counts, as well as methods to acknowledge and disable all connected Alarms

connected to it

. These

fields

functionalities can be

associated with

linked to buttons to manage Alarms. You can check these possibilities out by double-clicking this example’s components in Draw mode and looking at their Dynamics and text fields.
Additionally, Areas can be used to filter AlarmItems,

making

simplifying and organizing the

visualization

contents of AlarmViewers

simpler and more organized. On

. To do this, go to Displays → Draw → Modules, select an AlarmAreas component and place it on the desired display. Set the SelectedArea field to a text tag, and then apply it to the AlarmAreas through the display’s CodeBehind, like this:

Code Block
public async void ApplyFilterButtonDown(object sender, System.Windows.Input.MouseButtonEventArgs e)
{
	 if(String.IsNullOrEmpty(@Tag.SelectedArea))
	 	 @Tag.AlarmFilter = "";
	 else
	 	 @Tag.AlarmFilter = @Alarm.Area[@Tag.SelectedArea].GetFilter();
}

This code accesses retrieves the Area selected by the user through the AlarmAreas component. Then, method GetFilter returns text filtering The GetFilter method then generates a text filter that includes the selected Area and all of its SubAreas. This filter is passed assigned to the AlarmFilter text tag AlarmFilter, which is applied to the AlarmViewer by double-clicking on it in Draw mode and setting its Filter field to {Tag.AlarmFilter}.


Reference Information

Check out the Alarms Alarm Areas documentation to leverage this feature's potential and AlarmAreas Control for more information on the purpose and behavior of AlarmAreas.