Overview
When any Tag is registered into a Historian module to record the value over time or events, it is called HistorianTag.The HistorianTag can be any of this types: INT, Digital, Decimal or Textbecome a Historian Tag. On this page you find how to configure a new Historian Tag and the properties available.
On this page:
Table of Contents | ||||
---|---|---|---|---|
|
Understanding Historian Tags
When any Tag is registered into a Historian module to record the value over time or events, it is become a Historian Tag.Historian Tags are used when you need to archive data, especially when dealing with process control and manufacturing, but not restricted to. You have the option to archive the following Historian Tag types:
- Integer
- Decimal (float)
- Text (string)
- Digital (boolean)
When you use Historian Tags, you archive data by associating information with specific tags and tables. In other words, you establish a link between Tags and Historian Tables to ensure systematic and organized data storage. You can also archive Template Template Tags. For this case, you can specify one of the Tamplate TagTemplate Tag's properties or archive all properties by entering only the main Tag name.
To utilize Historian Tags, you need to define which Tags are associated with each Historian Table.
Historian Tags allow users to archive data effectively. To add a tag, users enter the TagName and select a Historian table. This interface offers flexibility with optional settings and supports the use of template tags for storing specific properties or all properties associated with a main tag name.
Definition
Historian Tags is a tool that facilitates the archiving of data by associating it with specific tags and tables.
Purpose
The purpose of Historian Tags is to facility the store data.
Function
Historian Tags function by linking tags to a table into the ArchiveLocation.
Operation
Users operate Historian Tags by entering a tag name and choosing a Historian table for archiving. For template tags, users either select a specific property or store all properties by entering the main tag name.
Application
Historian Tags apply in scenarios where data collection, archiving, and retrieval are necessary. They are crucial in fields like process control, manufacturing, and other industrial applications where historical data analysis is essential.
Usage
To use Historian Tags, go to Historian → Historian Tags, enter the tag name, select a Historian table, and configure additional settings if needed. For template tags, users specify whether to store specific properties or all associated properties.
Configuring Historian Tags
Before setting Historian Tags, you need to configure the Historian Tables. However, you can to use the default one (Table1) if you prefer.
After configuring the Historian Tables, you can start defining which Tags to archive with the configured Historian Tables. To add and configure a single Tag, follow the steps below:
- Access Historian → Historian Tags.
- On the TagName column, type the Tag name or select from the available list. Alternatively, you can copy and past the Tag's name from Unified Namespace → Tags.
- Configure the DeadBand, Deviation, and RateOgChange. The following section describes each of these configurations.
- Select if FrameworX should consider an Absolute or Percentual as the DeviationDeadBandType.
- To finish, select the HistorianTable where the Tag's information will be archived.
Info | ||
---|---|---|
| ||
Only the TagName and HistorianTable fields are mandatory. |
The image below illustrates the process described above.
Historian Tags properties
When configuring a Historian Tag, you need to specify some properties which that will define how data will be archived. The following table describes each available property you can configure:
If necessary, configure more settings, but in general cases it is not necessaryProperty | Description | ||
---|---|---|---|
TagName | Enter a tag name or click ... to select a tag. | Specify the unique identifier of the Tag to be archived. To archive Template Tags, specify one of the Template Tag's properties or archive all properties by entering only the main Tag name. | |
DeadBand | (Optional feature) Defines | DeadBand | When using the Save on Change option in the historian table, the DeadBand is how much the value must change (in Units) for the system to store the value. This configuration is considered when you use the Save on Change option in the historianHistorian Table. |
Deviation | When using the Time DeadBand option in the historian table, the Deviation is (Optional feature) Specify how much the value must change (in Units) for the system to store the value. This configuration is considered when you use the Time DeadBand option in the historian. This Historian Table. If you define this property, its value overrides the Time Deadband logging interval. | ||
RateOfChange | When using the Time DeadBand option in the historian table, the RateOfChange is (Optional feature) Defines how much the value must change (in Units) by second , for the system to store the value. This configuration is considered when you use the Time DeadBand option in the historian. This Historian Table. If you define this property, its value overrides the Time Deadband logging interval. | ||
DeviationDeadBandType | (Optional feature) Determines the calculation method used to define the deadband value. | ||
HistorianTable | Select the table that has the settings you want Historian Table to use for when to save and how long to retain this tag's value. | ||
[Other columns] | For definitions of other columns that are available in many tables, see Common Column Definitions. |
Adding Tags for Data Logging
After you configure your tables for the tag historian, you can configure the tags that will be logged.
To configure the tags for the tag historian:
when saving the Tag's value. |
In this section...