This document has only the specific information about the device connection settings and its address syntax.

Refer to the User Guide for more information on the Device Module.



Summary

Communication Driver Information

Driver name

Siemens

Assembly Name

T.ProtocolDriver.Siemens

Assembly Version

2.2.2.0

Available for Linux

False

Devices supported 

S7 300/400

Third-party libraries

AGL4DotNET.dll, AGLink40.dll and AGLink40_x64.dll.

Manufacturer

Siemens

Protocol

Proprietary over TCP/IP

PC Requirements

Ethernet port


Channels Configuration

Protocol Options

  • Device Number: Used for connection when there is more than one PLC in the network.
  • PLC Number: Slave PLC number



Nodes Configuration

Station Configuration

Station syntax: <IP  Address> ; <Rack>; <Slot>

Where :

  • <IP Address>: IP address of the slave device in the Siemens network
  •  <Rack>: Rack of the device
  •  <Slot>: Slot of the device



Points Configuration

Address

The syntax for the Siemens communication points is: <Type>:<Format><Address>.< Bit or String Length >

For DataBlock type: DB<DB Group>:<Format><Address>.<Bit or String Length>

Where:

  • <Type>  is the register type. Valid values are: 
    • M=Flags
    • T=Timers
    • C=Counters
    • I=Inputs
    • Q=Outputs
    • DB=Data Blocks.
  • <DB Group> is the group number of the configured Data Block type.
  • <Address> is the device address.
  • <Format>  is the format to treat the value from or to the device. Valid values are:
    • B=Byte
    • W=Word
    • DW=Dword
    • F=Float
    • ST=String
  • <Bit or String Length> is the bit number. This parameter is optional. If you use the String type, it represents the String length.



Driver Revision History

Siemens Revision History

Version 

Notes

2.2.2.0

Initial release on new documentation standards.