This document has only the specific information about the device connection settings and its address syntax.
Refer to the User Guide for more information on the Device Module or on UNS TagProvider Connections.
On this page:
Communication Driver Information | |
---|---|
Driver name | MitsubishiFXSerial |
Assembly Name | T.ProtocolDriver.MitsubishiFXSerial |
Assembly Version | 1.0.1.0 |
Available for Linux | False |
Devices supported | FX3U |
Manufacturer | Mitsubishi |
Protocol | Proprietary |
PC Requirements | Standard Serial Port |
Operand | Read | Write | Data Type | Address size |
D - Data register | Yes | Yes | Word | 2 bytes |
TN – Timer Current value | Yes | Yes | Word | 2 bytes |
TS – Timer Contact | Yes | No | Bit | 1 bit |
CN – Counter Current value | Yes | Yes | Word | 2 bytes |
CS – Counter Contact | Yes | No | Bit | 1 bit |
X - Input relay | Yes | No | Bit | 1 bit |
Y - Output relay | Yes | Yes | Bit | 1 bit |
M - Internal relay | Yes | Yes | Bit | 1 bit |
S0 - Annunciator | Yes | Yes | Bit | 1 bit |
Maximum size of blocks: Defines the maximum of addresses in a read block.
The syntax for the Mitsubishi FX Serial communication points is: <Operand> <Address>
Where :
Operand |
---|
D - Data register |
TN – Timer Current value |
TS – Timer Contact |
CN – Counter Current value |
CS – Counter Contact |
X - Input relay |
Y - Output relay |
M - Internal relay |
S0 - Annunciator |
Note: The Y Operand is an Octal Numeral System.
MitsubishiFX_Serial Revision History | |
---|---|
Version | Notes |
1.0.1.0 | Initial release on new documentation standards |