Summary Information

Communication Driver Name: Siemens

Current Version: 2.2.2.0

Implementation DLL: T.ProtocolDriver. Siemens.dll

Third Party Libraries: AGL4DotNET.dll, AGLink40.dll, and AGLink40_x64.dll

Interface: TCPIP

PLC types supported: Devices S7 300/400/1200/1500

Manufacturer: Siemens

PC Hardware requirements: Ethernet board



Channel Configuration

Protocol Options

Device Number: Used for connection when there is more than one PLC in the network

PLC Number: Slave PLC number



Node Configuration

Station Configuration

Station syntax: <IP Address>;<Rack>;<Slot>;<S7 Family>

Where:

300/400: Support for PLC Siemens S7-300 and S7-400 Series

1200: Support for PLC Siemens S7-1200 and S7-1500 Series



Point Configuration

Address

The syntax for the Siemens communication points is: <Type>:<Format><Address>.<Bit or String Length>

For DataBlock type: DB<DB Group>:<Format><Address>.<Bit or String Length>

Where:



Troubleshoot

The status of the driver execution can be observed through the diagnostic tools, which are:

• Trace window
• Property Watch
• Module Information


The above tools indicate if the operations have succeeded or have failed. A status of 0 (zero) means communication is successful. Negative values indicate internal driver errors, and positive values indicate protocol error codes.