The software platform establishes Channels to manage communication using protocols. A DeviceChannel object encapsulates a selected Protocol and its configuration settings. The Channel is the next step of the Device Module configuration, mapping the stations of PLCs or devices in a field network, and allowing the selection of the protocol settings that will be used with each device.
On this page:
Device Channels are the pathways for communication between the HMI and the devices in the system. The sections below describe how to create and edit Device Channels on the platform in more detail.
To create a new channel, follow these steps:
To configure or edit an existing channel, follow these steps
The following table describes each available property you can configure when editing a channel:
Field | Description | |
---|---|---|
Protocol Options | Defines the options for this protocol. The options depend on the selected protocol. Check each protocol documentation to guide you. | |
Interface | Defines the interface type for this channel. Serial: Use this option to configure the serial parameters for RS232/485 networks. Multi Serial: Use this for configurations with multiple RS-232 ports. TCPIP: Use for Ethernet or wireless networks. | |
Settings | Defines the settings for this channel. The available values will depend on the interface the channel is using. For a serial interface, typically keep the defaults. For a Multi Serial interface, enter the number of RS-232 ports to use in the Ports field. Node Connection: The number of parallel requests sent to each node (asynchronous communication). Accept Unsolicited: Allow to accept unsolicited input from the slave. Listening Port: The TCP port where the slave device is connected (default is 502). Node Connection: The number of parallel requests sent to each node (asynchronous communication). Max Simultaneous Connections: The maximum number of concurrent connections. Share Node Same IP: Several slaves are connected to a single IP address. For example, RS485/Ethernet Converters. Use Single Thread: Use a single thread for the same IP nodes. Use Ping To Check Connection: Check for connection before sending a packet.
| |
Timeout | Defines the timeout options for this channel. Typically, keep the default value. | |
InitialState | Defines the initial state for this channel, the states can be as follows: Enabled: The channel is loaded and execution starts when the project starts. Disabled: The channel is loaded, but does not starts execution going the disabled state. Remote: The channel is local in a remote Computer defined that the Remote Settings. See Remote Channels page. Reserved: The channel is not loaded, it acts as the channel was temporarily deleted from the project. | |
RemoteSettings | Defines the primary IP and backup IP to configure the remote computer where this channel will run. | |
DriverVersion | Defines the version of the current driver being used. |
After creating a solution, you may face issues that compromise the communication with the field device. In such moments, instead of restarting the entire system, you may solve the problem by restarting the channel. You can perform such tasks using scripts, avoiding shutting down the entire system. To do so, follow these steps:
Create a new class using the C# code below, where "XXXX" refers to the name of the channel.
@Device.Channel.XXXX.Stop() @Device.Channel.XXXX.Start() |
You can create a Task or Expression to call this class when needed and do it in other ways that don't use the class.
See the Remote Channels page for more information.
public void Stop() { @Device.Channel.ControlLogix.Stop(10); } |