Client connector for IEDs, RTUs and I/O devices that use IEC 61850 Edition 2 over MMS.
Modules → Electrical Pack → IEC 61850 Client
The IEC 61850 Client connector implements the ACSI core services of the IEC 61850 standard, mapped to MMS as defined in part 8-1 of the standard, over TCP/IP. It acts as a client station and communicates with IEDs (Intelligent Electronic Devices), RTUs (Remote Terminal Units) and I/O devices that act as IEC 61850 servers.
Communication Driver Information | |
|---|---|
Driver name | IEC 61850 Client Communication Protocol |
Assembly Name | T.ProtocolDriver.IEC61850 |
Protocol interface | IEC 61850 Edition 2 over TCP/IP |
Max number of nodes | User defined |
Requirements | Ethernet port |
This page describes the device connection settings and the address syntax of this connector.
For further information, see:
There are two independent ways to use this protocol:
This page covers the device configuration for both methods.
This topic summarizes the parts of the IEC 61850 standard that directly affect the definition and implementation of this connector. For details and a formal description, refer to the standard or to the documentation of the server IEDs. The standard has ten parts:
Part | Description |
|---|---|
1 | Introduction and overview |
2 | Glossary |
3 | General requirements |
4 | System and project management |
5 | Communication requirements for functions and device models |
6 | Configuration description language for communication in substations related to IEDs |
7.1 | Basic communication structure for substation and feeder equipment: Principles and models |
7.2 | Basic communication structure for substation and feeder equipment: Abstract communication service interface |
7.3 | Basic communication structure for substation and feeder equipment: Common data classes |
7.4 | Basic communication structure for substation and feeder equipment: Compatible logical node classes and data classes |
8.1 | Mapping to MMS (ISO/IEC 9506-1 and ISO/IEC 9506-2) and to ISO/IEC 8802-3 |
9.1 | Sampled values over serial unidirectional multidrop point-to-point link |
9.2 | Sampled values over ISO/IEC 8802-3 |
10 | Conformance testing |
For data communication between computers and IEDs, the standard defines the following message types:
Message | Description |
|---|---|
GOOSE (Generic Object Oriented Substation Event) | Multicast messages that carry information between IEDs. They carry only the messages that report the operation of a protection function or a digital signal. |
MMS (Manufacturing Message Specification) | Unicast messages that exchange measurement (analog) or state (digital) data, to report the state of equipment and process. |
In IEC 61850, the points inside an IED are not addressed by numbers, as in other protocols. They are objects, addressed by names that the standard defines. An IEC 61850 IED holds a map of objects arranged in a hierarchy. In the communication between a client (for example, a SCADA system) and a server (for example, a digital relay IED), these object names travel in the protocol messages, at least while the communication is being established.
An object reference names each level of the hierarchy in order: logical device, logical node, functional constraint, data object and data attribute. For example, in Relay1/XCBR1$ST$Pos$stVal, Relay1 is the logical device, XCBR1 the logical node, ST the functional constraint, Pos the data object and stVal the data attribute.
FC | Description |
|---|---|
ST | Status information |
MX | Measurands (analog values) |
CO | Control: the DataAttribute is operated (control model) and read |
SP | Setpoint: the DataAttribute represents a set-point; the value may be controlled and read |
SV | Substitution: the DataAttribute represents a substitution |
CF | Configuration: the DataAttribute represents a configuration |
DC | Description: the DataAttribute represents a description |
SG | Setting group: logical devices that implement the SGCB class |
SE | Setting group (editable) |
EX | Extended definition |
BR | Buffered report |
RP | Unbuffered report |
LG | Logging: the attribute represents a log control |
GO | GOOSE control: the attribute represents a GOOSE control |
GS | GSSE control: the attribute represents a GSSE control |
MS | Multicast sampled value control |
US | Unicast sampled value control |
The connector has two libraries that work together: the Communication library and the Integration library.
The Communication library handles the communication between the connector and the equipment. It follows edition 2 of the IEC 61850 standard series.
Supported objects
IEC 61850 Object | MMS Object |
|---|---|
SERVER class | Virtual Manufacturing Device (VMD) |
LOGICAL DEVICE class | Domain |
LOGICAL NODE class | Named Variable |
DATA class | Named Variable |
DATA-SET class | Named Variable List |
SETTING-GROUP-CONTROL-BLOCK class | Named Variable |
REPORT-CONTROL-BLOCK class | Named Variable |
LOG class | Journal |
LOG-CONTROL-BLOCK class | Named Variable |
GOOSE-CONTROL-BLOCK class | Named Variable |
GSSE-CONTROL-BLOCK class | Named Variable |
CONTROL class | Named Variable |
Files | Files |
Supported ACSI (Abstract Communication Service Interface) services
IEC 61850 Model | ID | IEC 61850 Service | AA: TP / MC | Client | Server |
|---|---|---|---|---|---|
Server | S1 | ServerDirectory | TP | ? | ? |
Application association | S2 | Associate | TP | ? | ? |
S3 | Abort | TP | ? | ? | |
S4 | Release | TP | ? | ? | |
Logical device | S5 | LogicalDeviceDirectory | TP | ? | ? |
Logical node | S6 | LogicalNodeDirectory | TP | ? | ? |
S7 | GetAllDataValues | TP | ? | ? | |
Data | S8 | GetDataValues | TP | ? | ? |
S9 | SetDataValues | TP | ? | ? | |
S10 | GetDataDirectory | TP | ? | ? | |
S11 | GetDataDefinition | TP | ? | ? | |
Data set | S12 | GetDataSetValues | TP | ? | ? |
S13 | SetDataSetValues | TP | ? | ? | |
S14 | CreateDataSet | TP | ? | ? | |
S15 | DeleteDataSet | TP | ? | ? | |
S16 | GetDataSetDirectory | TP | ? | ? | |
Substitution | S17 | SetDataValues | TP | ? | ? |
Setting group control block | S18 | SelectActiveSG | TP | ? | ? |
S19 | SelectEditSG | TP | ? | ? | |
S20 | SetSGValues | TP | ? | ? | |
S21 | ConfirmEditSGValues | TP | ? | ? | |
S22 | GetSGValues | TP | ? | ? | |
S23 | GetSGCBValues | TP | ? | ? | |
Buffered report control block (BRCB) | S24 | Report | TP | ? | ? |
S24-1 | data-change (dchg) | TP | ? | ? | |
S24-2 | quality-change (qchg) | TP | ? | ? | |
S24-3 | data-update (dupd) | TP | ? | ? | |
S25 | GetBRCBValues | TP | ? | ? | |
S26 | SetBRCBValues | TP | ? | ? | |
Unbuffered report control block (URCB) | S27 | Report | TP | ? | ? |
S27-1 | data-change (dchg) | TP | ? | ? | |
S27-2 | quality-change (qchg) | TP | ? | ? | |
S27-3 | data-update (dupd) | TP | ? | ? | |
S28 | GetURCBValues | TP | ? | ? | |
S29 | SetURCBValues | TP | ? | ? | |
Log control block | S30 | GetLCBValues | TP | ? | ? |
S31 | SetLCBValues | TP | ? | ? | |
S32 | QueryLogByTime | TP | ? | ? | |
S33 | QueryLogAfter | TP | ? | ? | |
S34 | GetLogStatusValues | TP | ? | ? | |
GOOSE control block | S35 | SendGOOSEMessage | MC | ? | ? |
S36 | GetGoReference | TP | |||
S37 | GetGOOSEElementNumber | TP | |||
S38 | GetGoCBValues | TP | ? | ? | |
S39 | SetGoCBValues | TP | ? | ? | |
GSSE control block | S40 | SendGSSEMessage | MC | ||
S41 | GetGsReference | TP | |||
S42 | GetGSSEElementNumber | TP | |||
S43 | GetGsCBValues | TP | |||
S44 | SetGsCBValues | TP | |||
Multicast SVC | S45 | SendMSVMessage | MC | ? | |
S46 | GetMSVCBValues | TP | ? | ? | |
S47 | SetMSVCBValues | TP | ? | ? | |
Unicast SVC | S48 | SendUSVMessage | TP | ? | |
S49 | GetUSVCBValues | TP | ? | ? | |
S50 | SetUSVCBValues | TP | ? | ? | |
Control | S51 | Select | TP | ? | ? |
S52 | SelectWithValue | TP | ? | ? | |
S53 | Cancel | TP | ? | ? | |
S54 | Operate | TP | ? | ? | |
S55 | Command-Termination | TP | ? | ? | |
S56 | TimeActivated-Operate | TP | ? | ? | |
File transfer | S57 | GetFile | TP | ? | ? |
S58 | SetFile | TP | ? | ? | |
S59 | DeleteFile | TP | ? | ? | |
S60 | GetFileAttributeValues | TP | ? | ? | |
Time | T1 | Time resolution of internal clock | 1 ms | 1 ms | |
T2 | Time accuracy of internal clock | ||||
T3 | Supported timestamp resolution | 1 ms | 1 ms |
AA: application association. TP: two-party application association (MMS over TCP/IP, or Unicast Sampled Values over Ethernet). MC: multicast application association (GOOSE or Sampled Values using multicast messages over Ethernet). ?: supported.
The Integration library connects the connector to FrameworX. It transfers the values read from and written to the equipment. In the tables below, a check mark (?) means the object or service is implemented.
Implemented objects
IEC 61850 Object | Implemented |
|---|---|
SERVER class | |
LOGICAL DEVICE class | ? |
LOGICAL NODE class | ? |
DATA class | ? |
DATA-SET class | ? |
SETTING-GROUP-CONTROL-BLOCK class | |
REPORT-CONTROL-BLOCK class | ? |
LOG class | |
LOG-CONTROL-BLOCK class | |
GOOSE-CONTROL-BLOCK class | |
GSSE-CONTROL-BLOCK class | |
CONTROL class | ? |
Files |
Implemented ACSI services
IEC 61850 Model | ID | IEC 61850 Service | Implemented |
|---|---|---|---|
Server | S1 | ServerDirectory | ? |
Application association | S2 | Associate | ? |
S3 | Abort | ? | |
S4 | Release | ? | |
Logical device | S5 | LogicalDeviceDirectory | ? |
Logical node | S6 | LogicalNodeDirectory | ? |
S7 | GetAllDataValues | ? | |
Data | S8 | GetDataValues | ? |
S9 | SetDataValues | ? | |
S10 | GetDataDirectory | ? | |
S11 | GetDataDefinition | ? | |
Data set | S12 | GetDataSetValues | ? |
S13 | SetDataSetValues | ||
S14 | CreateDataSet | ||
S15 | DeleteDataSet | ||
S16 | GetDataSetDirectory | ? | |
Substitution | S17 | SetDataValues | |
Setting group control block | S18 | SelectActiveSG | |
S19 | SelectEditSG | ||
S20 | SetSGValues | ||
S21 | ConfirmEditSGValues | ||
S22 | GetSGValues | ||
S23 | GetSGCBValues | ||
Buffered report control block (BRCB) | S24 | Report | ? |
S24-1 | data-change (dchg) | ? | |
S24-2 | quality-change (qchg) | ? | |
S24-3 | data-update (dupd) | ? | |
S25 | GetBRCBValues | ? | |
S26 | SetBRCBValues | ? | |
Unbuffered report control block (URCB) | S27 | Report | ? |
S27-1 | data-change (dchg) | ? | |
S27-2 | quality-change (qchg) | ? | |
S27-3 | data-update (dupd) | ? | |
S28 | GetURCBValues | ? | |
S29 | SetURCBValues | ? | |
Log control block | S30 | GetLCBValues | |
S31 | SetLCBValues | ||
S32 | QueryLogByTime | ||
S33 | QueryLogAfter | ||
S34 | GetLogStatusValues | ||
GOOSE control block | S35 | SendGOOSEMessage | |
S36 | GetGoReference | ||
S37 | GetGOOSEElementNumber | ||
S38 | GetGoCBValues | ||
S39 | SetGoCBValues | ||
GSSE control block | S40 | SendGSSEMessage | |
S41 | GetGsReference | ||
S42 | GetGSSEElementNumber | ||
S43 | GetGsCBValues | ||
S44 | SetGsCBValues | ||
Multicast SVC | S45 | SendMSVMessage | |
S46 | GetMSVCBValues | ||
S47 | SetMSVCBValues | ||
Unicast SVC | S48 | SendUSVMessage | |
S49 | GetUSVCBValues | ||
S50 | SetUSVCBValues | ||
Control | S51 | Select | ? |
S52 | SelectWithValue | ? | |
S53 | Cancel | ||
S54 | Operate | ? | |
S55 | Command-Termination | ||
S56 | TimeActivated-Operate | ||
File transfer | S57 | GetFile | |
S58 | SetFile | ||
S59 | DeleteFile | ||
S60 | GetFileAttributeValues | ||
Time | T1 | Time resolution of internal clock | |
T2 | Time accuracy of internal clock | ||
T3 | Supported timestamp resolution |
Implemented Functional Constraints: a check mark (?) means the connector reads or writes the attributes of that Functional Constraint.
Functional Constraint | Description | Read | Write |
|---|---|---|---|
BL | Blocking | ||
BR | Buffered report | ? | ? |
CF | Configuration | ? | ? |
CO | Control | ? | |
DC | Description | ? | ? |
EX | Extended definition | ? | ? |
LG | Log control blocks | ||
MS | Multicast SV | ||
MX | Measurands (analog values) | ? | |
OR | Operate received | ||
RP | Unbuffered report | ? | ? |
SE | Setting group editable | ||
SG | Setting group | ||
SP | Setpoint | ? | ? |
SR | Service response / Service tracking | ||
ST | Status information | ? | |
SV | Substitution | ||
US | Unicast SV |
The connector runs the following sequence:
Step | Purpose | Description |
|---|---|---|
1 | Channel initialization | The connector reads the channel settings and its configuration file, T.ProtocolDriver.IEC61850.config.xml, and validates them. |
2 | Node initialization | The connector connects to the equipment and reads its data structure. The connector needs this read to operate. This step repeats until it succeeds; only then does the connector go to the next step. |
3 | Point initialization | The connector reads and validates the registered points. It also checks that each point exists in the equipment and that the connector can read or write it. |
4 | Start of the read and write tasks | The task that reads COMTRADE files and points starts according to the node settings. The write task starts and runs when a point with write access changes value. The task that reads received reports starts, and the report points are subscribed. |
5 | Cyclic execution of the tasks | The read and write tasks run as configured. If the connection is lost, the connector returns to step 2. |
Item | Description | Default |
|---|---|---|
Logging level | Debug: all messages are recorded in the log. | Info |
Log files | Maximum number of log files kept before the oldest one is deleted. | 30 |
Log file size | Maximum size of each log file. Specify the size with the suffix KB, MB or GB. | 35MB |
Command password | Adds a check to commands. Enter a numeric password of up to 9 digits. When a command arrives, the connector compares it with the current value of the EstimatedValue property of the tag that sends the command. A display, script or other source that sends the command must first write the password to that property. After it runs the command, the connector sets EstimatedValue to zero. When the option is empty or zero, the check is not made. | Empty |
Command timeout (s) | Maximum time, in seconds, for a command to run. | 10 |
Command originator | Originator category that the connector sends with control commands: Remote or Station. | Station |
Tls Enabled | Enables encryption of the communication based on TLS (Transport Layer Security). Client and server must both enable it. The next three options then name text files with the keys and certificates, placed in the solution folder. | Disabled |
Tls OwnKey | Name of the file with the client's own key. | Empty |
Tls OwnCertificate | Name of the file with the client's own certificate. | Empty |
Tls CACertificate | Name of the file with the CA certificate used to validate the chain. | Empty |
For command security, the connector also checks the timestamp of the output tag. This is the time of the tag's last value change, and the change must have happened at most 30 seconds before the connector receives the command request. |
CustomTCPIP.
Enabled.
Open the PrimaryStation column of the node to set the following options:
Item | Description | Default |
|---|---|---|
IP | IP address of the IED. | 0.0.0.0 |
Port | TCP port of the IED. | 102 |
Connection timeout (ms) | Maximum time, in milliseconds, to establish the TCP/IP connection with the IED. Minimum 1000. | 5000 |
Connection password | Password used to authenticate the client with the IED (IEC 61850 Edition 2). | Empty |
Reading mode | Polling/Report: reads by polling and by report. | Polling/Report |
Analog read polling rate (ms) | Period, in milliseconds, of the read requests for analog input points (AI). A value of 0 disables this read. | 60000 |
Digital read polling rate (ms) | Period, in milliseconds, of the read requests for binary input points (BI). A value of 0 disables this read. | 30000 |
Datasets read polling rate (ms) | Period, in milliseconds, of the read requests for DataSet points of type DS. A value of 0 disables this read. | 600000 |
Dataset T1 read polling rate (ms) | Period, in milliseconds, of the read requests for DataSet points of type DS1. A value of 0 disables this read. | 660000 |
Dataset T2 read polling rate (ms) | Period, in milliseconds, of the read requests for DataSet points of type DS2. A value of 0 disables this read. | 720000 |
Dataset T3 read polling rate (ms) | Period, in milliseconds, of the read requests for DataSet points of type DS3. A value of 0 disables this read. | 780000 |
Dataset T4 read polling rate (ms) | Period, in milliseconds, of the read requests for DataSet points of type DS4. A value of 0 disables this read. | 840000 |
Report polling rate (ms) | Period, in milliseconds, of the check that the report points are enabled. The connector reads the RptEna attribute of each report point. A value of 0 disables the cyclic check; the connector then enables and subscribes to the reports only once, during initialization. | 5000 |
Communication status tag | Name of an existing Digital tag that receives the communication status: 0 = offline, 1 = online. | Empty |
Last command error tag | Name of an existing Integer tag that receives the error code of the last command. See Command Errors (CO) under Error and Quality Codes. | Empty |
SCL file name to config points | Name of the SCL file the address browser of the Points table reads. The connector looks for the file in the solution folder. To use another folder, enter the full path. | Empty |
Force autodescription on connection loss | Enabled: the connector reads the data model of the IED again after a connection loss. | Disabled |
Validate TimeQuality | Enabled: the connector checks the time quality of the timestamps and logs a warning when it reports ClockFailure or ClockNotSynchronized. | Disabled |
Quality changes timestamp | Enabled: the timestamp of a point is updated when only its quality changes. | Disabled |
Ignore polling on points updated by reports | Enabled: polling read requests are skipped for points updated by enabled reports. Performance is better, but read data integrity is lower. | Disabled |
COMTRADE files reading mode | Download: the connector transfers the COMTRADE files to the computer. | Download |
COMTRADE files download folder | Folder on the computer where the transferred COMTRADE files are saved, for example | Empty |
COMTRADE files download polling rate (ms) | Period, in milliseconds, of the check for new COMTRADE files. A value of 0 disables this read. | 0 |
FTP username | User allowed to read the COMTRADE files over FTP. When this field is filled in, the files are read over FTP; otherwise, they are read over MMS. | Empty |
FTP password | Password of the FTP user. | Empty |
Connection AP-Title | AP-Title used in the connection. When empty, the connector uses 1,1,1,999,1. | Empty |
Connection AE-Qualifier | AE-Qualifier used in the connection. When empty, the connector uses 12. | Empty |
Command interlock check | Enabled: the interlock check flag is set on Select and Operate commands. | Enabled |
Command synchro check | Enabled: the synchrocheck flag is set on Operate commands. | Enabled |
SampleValuesSubscriber | Enables the Sampled Values subscriber. | Disabled |
Send PurgeBuf on Start | Disabled: when the connector starts, it sends the last EntryID received for each buffered report. The IED keeps the earlier events in its buffer but knows that this client already received the events up to that EntryID. | Disabled |
Force float32 for SetPoints | Disabled: set points are sent in their native type, Float32 or Float64. | Disabled |
A secondary station, when the installation has one, accepts the same settings as the primary station.
This protocol supports the Tag Provider function, which gives access to the data model of a device without creating solution tags.
To use the IEC 61850 protocol as a Tag Provider, go to Unified Namespace → Tag Providers and create a provider for this protocol. Set the PrimaryStation column with the options below.
Item | Description | Default |
|---|---|---|
IP | IP address of the IED. | 0.0.0.0 |
Port | TCP port of the IED. | 102 |
ConnectionTimeout | Maximum time, in milliseconds, to establish the TCP/IP connection with the IED. Minimum 1000. | 5000 |
ConnectionPassword | Password used to authenticate the client with the IED (IEC 61850 Edition 2). | Empty |
ReadingMode | Polling/Report: reads by polling and by report. | Polling/Report |
AnalogReadPollingRate | Period, in milliseconds, of the read requests for analog points. A value of 0 disables this read. | 60000 |
DigitalReadPollingRate | Period, in milliseconds, of the read requests for digital points. A value of 0 disables this read. | 30000 |
DatasetsReadPollingRate | Period, in milliseconds, of the read requests for DataSets. A value of 0 disables this read. | 600000 |
ReportPollingRate | Period, in milliseconds, of the check that the reports are enabled, made by reading the RptEna attribute. A value of 0 disables the cyclic check; the reports are then enabled and subscribed only once, during initialization. | 5000 |
CommandPassword | Numeric password that allows commands. | Empty |
UseSCLfileToConfiguration | Enabled: the provider reads the data model from the SCL file named in SCLConfigFileName. | Not set |
SCLConfigFileName | Full path and name of the SCL configuration file. | Empty |
SCLServerName | Name of the IED server for this provider, used when the SCL file describes more than one IED. | Empty |
ConnectionAPTitle | AP-Title used in the connection. When empty, the connector uses 1,1,1,999,1. | Empty |
ConnectionAEQualifier | AE-Qualifier used in the connection. When empty, the connector uses 12. | Empty |
CommandInterlockCheck | Enabled: the interlock check flag is set on Select and Operate commands. | Disabled |
CommandSynchroCheck | Enabled: the synchrocheck flag is set on Operate commands. | Disabled |
SampleValuesSubscriber | Enables the Sampled Values subscriber. | Disabled |
The command interlock and synchrocheck options default to Enabled on a device node and to Disabled on a Tag Provider. |
A secondary station, when the installation has one, accepts the same settings as the primary station.
The Points table maps each tag to the name of an IEC 61850 data object in a remote IED, which is either the source of the information or the target of a command.
The point address has two fields separated by a colon: Type and Address. Some point types add fields after the address.
The point type groups and classifies the IEC 61850 addresses. Points with write access are written when the tag changes value. Points with read access are read at the polling rate set in the node configuration.
Acronym | Name | Tag Type | Access | Description |
|---|---|---|---|---|
AI | Analog input | Double | Read | Analog input. |
BI | Binary input | Integer | Read | Digital input. |
AO | Analog output | Double | Write | Analog output. |
BO | Binary output | Digital | Write | Digital output. |
RP | Unbuffered report | Digital | Read | Unbuffered report. 0: report not subscribed. 1: report subscribed. |
BR | Buffered report | Digital | Read | Buffered report. 0: report not subscribed. 1: report subscribed. |
RPF | Unbuffered report flag | Digital, Integer or Text | Read | Attribute of an unbuffered report. |
BRF | Buffered report flag | Digital, Integer or Text | Read | Attribute of a buffered report. |
DS | DataSet | Digital | Read | Reads all points of the DataSet. |
DS1 | DataSet T1 | Digital | Read | Reads all points of the DataSet. |
DS2 | DataSet T2 | Digital | Read | Reads all points of the DataSet. |
DS3 | DataSet T3 | Digital | Read | Reads all points of the DataSet. |
DS4 | DataSet T4 | Digital | Read | Reads all points of the DataSet. |
INC | Integer output control | Integer | Write | 32-bit integer. |
BSC | Binary step position control | Integer | Write | 0: Stop. 1: Lower. 2: Higher. 3: Reserved. |
ISC | Integer step position control | Integer | Write | 8-bit integer, from -64 to 63. |
ASG | Analog setting | Double | Write | 32-bit real (single float). |
The BO type has an extra field, Command Parameter, which sets a fixed value that the command sends when the digital tag of the point changes value. In the address editor of the Points table, a BO point shows three fields: Type (BO), Item name (the object reference) and Command parameter. For example:
Step | Description | Column | Value |
|---|---|---|---|
1 | Create a tag in Unified Namespace → Tags | Name | BREAKER_OFF |
2 | Create a tag in Unified Namespace → Tags | Name | BREAKER_ON |
3 | Create a point in Devices → Points | TagName | BREAKER_OFF |
4 | Create a point in Devices → Points | TagName | BREAKER_ON |
Link BREAKER_OFF to an Off button and BREAKER_ON to an On button, both with a ToggleValue action. Each time the tag toggles between 0 and 1, the connector sends a command with the fixed value set in the address.
When the command parameter is empty, the connector sends the new value of the tag as the command parameter. |
The name of the control object in the point address selects the command mode:
Examples of addresses for each mode:
Mode | Address |
|---|---|
Cancel |
|
Oper |
|
SBOw |
|
To send only a Select, without the Operate, use an address that contains SBOw and add SO (Select Only) to the command parameter, for example BO:DemoProtCtrl/Obj3CSWI2$CO$Pos$SBOw$ctlVal:1:SO.
A DataSet is an object that holds a list of Data Object names, normally preconfigured in the server IEDs. The contents (state, measurement, timestamp, quality) of the Data Objects of a DataSet can be obtained in two ways:
DataSet points are read by polling and use the DS type. The DS1, DS2, DS3 and DS4 types allow a different read period for each group of DataSet points.
For each Report configured in the server that the client must receive, add an entry to the Points table. At runtime, this point holds the state of the Report (0: disabled, 1: enabled), read from the RptEna attribute of the Report at the Report polling rate set in the node configuration. The OptFlds and TrgOps attributes have these default values:
You can change these fields for each Report in the browser window of the Address column (see Reports Attributes Window).
Register these Report attributes as points to monitor and control the Report:
Attribute | Tag | Description |
|---|---|---|
EntryID | Text | Identifier of the received Report. It is required for the correct control of a Buffered Report: after a disconnection, the connector subscribes to the Report again from the last EntryID stored in the tag. Because the value must be kept, register the tag, make it retentive, and include it in the Points table. |
SqNum | Integer | Sequence number of the Reports. |
PurgeBuf | Integer | Required to send the PurgeBuf attribute to the enabled reports (see Send PurgeBuf on Start). Register a point with this address, like the other report flags. |
Create tags to receive these values, and register them in the Points table with the Report address followed by $ and the attribute name. For example:
Address | Use |
|---|---|
| Buffered report |
| EntryID of the report |
| Sequence number of the report |
Addresses follow the IEC 61850 format:
LogicalDevice/LogicalNode$FunctionalConstraint$DataObject$DataAttribute
Create a point in the Points table for each Data Object you need. Complex Data Objects, such as current or three-phase voltage measurements, have more than one level of Data Attributes. The connector recognizes some structures and reads each phase, but each Data Attribute in the first level below the Data Object must be a point in the Points table.
When the connector cannot tell which value of a structure to read, the point reports an error at initialization. In that case, register the address down to the attribute that holds the value. The quality and time are read from the structure that contains the attribute.
Example of an address registered down to the structure, IED7SJ63MEAS/MMXU1$MX$PhV$phsA:
IED7SJ63MEAS/MMXU1$MX$PhV$phsA$instCVal$mag$fIED7SJ63MEAS/MMXU1$MX$PhV$phsA$cVal$mag$fIED7SJ63MEAS/MMXU1$MX$PhV$phsA$qIED7SJ63MEAS/MMXU1$MX$PhV$phsA$tExample of an address registered down to the attribute, IED7SJ63MEAS/MMXU1$MX$PhV$phsA$cVal$mag$f:
IED7SJ63MEAS/MMXU1$MX$PhV$phsA$cVal$mag$fIED7SJ63MEAS/MMXU1$MX$PhV$phsA$qIED7SJ63MEAS/MMXU1$MX$PhV$phsA$tCreate two Access Types, Read and Write, and assign one of them to each point.
Property | Read | Write |
|---|---|---|
ReadOnStartup | True | False |
ReadEnable | Always | Never |
ReadPollingRate | 00:00:01.00 (one second) | |
WriteEventEnabled | False | True |
WriteEvent | Changed | Changed |
AcceptUnsolicited | False | False |
UseStaticBlocks | False | False |
Leave the other Access Type properties empty: ReadTrigger, ReadStatus, ReadCompleted, WriteTrigger, WriteStatus, WriteCompleted, BlockCommand and Description.
The IEC 61850 Browser Window helps you register the objects of an IEC 61850 server (IED). To open it from a record of the Points table:
The browser can navigate an IED or an SCL file. When the SCL file name to config points option holds a valid file name, the file button opens that file. When the node has an IED IP address, the IED button connects to the IED. The third button, with the circular arrow, reads the data again.
The window has two panels side by side. The left panel shows a tree with the IED data. When you click a branch, the right panel lists the objects available at that level. When it opens, the left panel shows the server of the node set in the Node field of the point record. Click the server name to expand the branch, which follows the IEC 61850 hierarchy:
The browser loads the Data Objects, Reports and DataSets configured in the server IED either by connecting to the IED or by reading an SCL (Substation Configuration Language) file. The supported files are ICD (IED Capability Description), SCD (Substation Configuration Description) and CID (Configured IED Description). Right-click the name of the current server to choose the source.
When you click the name of a server for the first time, the browser connects to the IED of that server. When the connection succeeds, the tree shows the Logical Devices of the server. Clicking a Logical Device reads all its objects.
A long load can mean a communication failure. Messages such as "Not connected" or "Time-out" appear at the bottom of the window, and the IED icon can show a red X. To try again, click the LD items again. If the connection problems persist, close and reopen the Browser Window.
To load the browser from an SCL file, enter its name in the SCL file name to config points option of the node, and place the file in the solution folder. When you click the server name, the browser reads the file and shows the Logical Devices. When you click an LD, the browser reads all the data objects below it.
To read the file from another folder, enter the full path in SCL file name to config points. The user that runs the application needs read and execute permission on that folder.
The server name in the channel does not need to match the name configured in the IED. When the names differ, or when an SCD file describes several IEDs, a window lists the IED names found in the file, and you choose the one for the node.
Navigate from the Logical Devices node to the Data Object you need, select it in the right panel and click OK to copy it to the Address field of the current record. The Node field must already hold the name of the target node. The right panel allows multiple selection: when you select more than one object, the browser creates a record in the Points table for each selected item.
The browser suggests the point type from the FC of the selected object. You can change the suggested type.
In the tree, after the data description, branches show the Reports (buffered and unbuffered) and the DataSets. A DataSet is a set of Data Objects preconfigured in the IED.
Clicking a DataSet name shows the Data Objects it contains, which are also listed in the right panel. To read a DataSet by polling, choose the DataSet name and create a record in the Points table, as described in Points Configuration.
Reports send unsolicited data from the server IEDs to the clients that enabled them. Each Report has attributes that define its behavior, including the name of the DataSet it sends. Each time the state of an object of that DataSet changes, the server sends a new instance of the Report to the client.
Click the RP (Unbuffered Reports) or BR (Buffered Reports) branch to see the Reports configured in the server IED. With a direct connection to the IED, first load the LDs that contain the Reports. If some reports do not appear, right-click the RP or BR branch and choose Refresh. An ICD file loads all data at once.
To choose a Report, use its name as it appears in the tree under the Logical Nodes, in BR or RP, or in the RP or BR branches after the LDs, where the names of the report control blocks appear in the right panel.
When you click a Report in the browser tree, the window with the attributes of the report control block opens. The left column lists the attribute names, and the center column (Current Values) shows their current values. Clicking an attribute in the right column opens a window to set a new value. The connector writes the new value to the server at the next runtime start of the client.
The connector stores the changed attributes in the Report address of the point: after the Report name, the address lists the name and value of each changed attribute. For example, this address changes the TrgOps and BufTm attributes:
BR:IED7SJ63CTRL/LLN0$BR$BRCBA01 $TRGOPS=[011110] $BUFTM=[+105]
The COMTRADE standard (IEEE Standard Common Format for Transient Data Exchange) defines a format for the data files and other files that describe faults, tests or simulations. Up to four file types can be generated:
When a protection relay records a disturbance in the power system, it stores a new oscillography file in its file directory. The connector checks the IED file directories periodically and transfers the new files to the computer.
The COMTRADE settings are in the node configuration (Primary Station):
At each check, the connector scans the IED file directories, over MMS or FTP, for files with the extensions HDR, CFG, DAT and INF, and saves them in the folder set in the node configuration.
When the file already exists in the folder, the connector compares its name and last modification date with those of the file in the IED to decide whether to transfer the file, or to delete it when the Download/Delete mode is set.
When the channel log level is Debug, these operations are recorded at Debug level in the log file. When FTP is used, a separate log file named FTP.log is created in the folder of each channel.
The connector records its log in text files and in the Windows Event Log. There are four message types:
Type | Description |
|---|---|
Debug | Lowest-level messages, to follow each process in detail. Used mainly by developers, testers and integrators. |
Info | Information messages to monitor the operation of the connector. |
Warning | Warning messages, to check or to ignore. |
Error | Error messages that need immediate attention and correction for the connector to operate correctly. |
The Trace Window runs on the server and shows the live operation log of each channel and node. Its columns Info 1, Info 2, Info 3 and Info 4 show the channel, the node, the point address and the method that the driver ran.
The connector always records all Warning and Error messages in the Windows Event Log, whatever the configured log level. The message format is: channel, node (when applicable), point address (when applicable), date and time, message type, thread, method and message.
Messages are recorded according to the Logging level of the channel.
The log folder has a subfolder for each channel and node that was initialized. The root is the Logs\Drivers\ folder of the solution.
The file name format is Log-DAY-MONTH-YEAR.log.
A new file starts each day. When the file reaches the Log file size, the connector copies it to a file with the suffix .1 and starts a new file. If the size is reached again on the same day, the new copy replaces the previous one. The Log files option limits how many files are kept: with 30 files of 35 MB, for example, the logs of each node use up to about 1050 MB of disk.
The message format is: point address (when applicable), date and time, message type, thread, method and message.
The connector reads command error codes from the LastApplError attribute, which only command data classes have. Its value shows the status of the last command and is updated when command responses arrive. Points with Functional Constraint CO use these codes, and the Last command error tag of the node receives them.
Code | Cause | Description |
|---|---|---|
0 | UNKNOWN | Unknown. |
1 | NOT_SUPPORTED | Not supported. |
2 | BLOCKED_BY_SWITCHING_HIERARCHY | Not successful, because one of the downstream Loc switches has the value TRUE. |
3 | SELECT_FAILED | Canceled because the selection (Select service) failed. |
4 | INVALID_POSITION | The control action is aborted because the switch position is invalid. |
5 | POSITION_REACHED | The switch is already in the intended position. |
6 | PARAMETER_CHANGE_IN_EXECUTION | The control action is blocked because a parameter change is running. |
7 | STEP_LIMIT | The control action is blocked because the tap changer has reached the limit EndPosR or EndPosL. |
8 | BLOCKED_BY_MODE | The control action is blocked because the LN is in a mode (Mod) that allows no switching. |
9 | BLOCKED_BY_PROCESS | The control action is blocked by an external event at process level that prevents a successful operation. |
10 | BLOCKED_BY_INTERLOCKING | The control action is blocked by the interlocking of switching devices. |
11 | BLOCKED_BY_SYNCHROCHECK | The control action with synchrocheck is aborted because the time limit was exceeded without the synchronism condition. |
12 | COMMAND_ALREADY_IN_EXECUTION | The Select or Cancel service is rejected because a control action is already running. |
13 | BLOCKED_BY_HEALTH | The control action is blocked by an internal event that prevents a successful operation (Health). |
14 | 1_OF_N_CONTROL | The control action is blocked because another control action in the same domain (for example, the substation) is already running. |
15 | ABORTION_BY_CANCEL | The control action is aborted by the Cancel service. |
16 | TIME_LIMIT_OVER | The control action is terminated because a time limit was exceeded. |
17 | ABORTION_BY_TRIP | The control action is aborted by a trip. |
18 | OBJECT_NOT_SELECTED | The control action is rejected because the control object was not selected. |
19 | OBJECT_ALREADY_SELECTED | The Select action is not run because the object is already selected. |
20 | NO_ACCESS_AUTHORITY | The control action is blocked because of missing access authority. |
21 | ENDED_WITH_OVERSHOOT | The control action ran, but the end position overshot. |
22 | ABORTION_DUE_TO_DEVIATION | The control action is aborted because of a deviation between the command value and the measured value. |
23 | ABORTION_BY_COMMUNICATION_LOSS | The control action is aborted because the connection with the client that issued it was lost. |
24 | ABORTION_BY_COMMAND | The control action is blocked because the data attribute CmdBlk.stVal is TRUE. |
25 | NONE | The command was not successful, for an unknown cause. |
26 | INCONSISTENT_PARAMETERS | The parameters of successive control services are not consistent, for example the ctlNum of the Select and the Operate services differ. |
27 | LOCKED_BY_OTHER_CLIENT | Another client has already reserved the object. |
99 | CONTROL_MODEL_STATUS_ONLY | The object is not controllable: only the services for a status object are supported, and the attribute ctlVal does not exist. |
The connector reports quality with the OPC (Open Platform Communications) quality codes. The table below maps the IEC 61850 qualities to the OPC codes.
IEC 61850 Quality | OPC Code | OPC Name | Description |
|---|---|---|---|
Validity Invalid, Detail Overflow | 0 | Bad [Non-Specific] | The value is bad, with no specific reason known. |
Config Error | 4 | Bad [Configuration Error] | There is a server-specific problem with the configuration, for example the item was deleted from the configuration. |
8 | Bad [Not Connected] | The input must be logically connected to a source but is not, so no value is available. | |
Detail Failure | 12 | Bad [Device Failure] | A device failure was detected. |
Time Quality (Clock Failure, Clock Not Synchronized) | 16 | Bad [Sensor Failure] | A sensor failure was detected. |
20 | Bad [Last Known Value] | Communication failed, but the last known value is available. | |
24 | Bad [Communication Failure] | Communication failed, and no last known value is available. | |
28 | Bad [Out of Service] | The item is off scan, locked or inactive. | |
32 | Bad [Waiting For Initial Data] | The source has not yet provided a first value for the item. | |
Validity Questionable | 64 | Uncertain [Non-Specific] | The value is uncertain, with no specific reason. |
Detail Old Data, Operator Blocked | 68 | Uncertain [Last Usable] | The source stopped updating the value, so the value is stale. |
Detail Out of Range, Detail Bad Reference, Detail Oscillatory, Detail Inconsistent, Detail Inaccurate | 80 | Uncertain [Sensor Not Accurate] | The value is at a sensor limit, or the sensor is known to be out of calibration. |
84 | Uncertain [EU Exceeded] | The value is outside the limits defined for the parameter. | |
88 | Uncertain [Sub-Normal] | The value comes from several sources and has fewer good sources than required. | |
Validity Good, Validity Test | 192 | Good [Non-Specific] | The value is good, with no special conditions. |
Source Substituted | 216 | Good [Local Override] | The value was overridden, typically with a manually entered value. |
Communication failure: when the connector has connected to the equipment and the communication then fails, the quality of the points changes to 24, Bad [Communication Failure]. The value and timestamp of the points do not change. If the connector never connected to the equipment, this is not a communication failure, and the quality of the points does not change.