Dashboard displays are the paradigm for data cards, not diagrams. Rows and columns of gauges, trends, KPIs, tables. Every element lives in a Cell, and cells are arranged in a responsive grid that reflows on window resize.
Use Dashboard when:
Use Canvas (load Skill Display Construction — Canvas instead) when equipment positions relative to each other matter (pipe A connects to vessel B), you're building a P&ID, or you need animation dynamics.
Prerequisite: load Skill Display Construction — Basics first.
The whole display is defined by:
Columns and Rows arrays describing the grid track sizesRow, Col, optional RowSpan/ColSpan, a Cell.HeaderLink for the card title, and Content (the element that fills the cell){
"Name": "OperationsOverview",
"PanelType": "Dashboard",
"DashboardDisplay": {
"Columns": ["*", "*", "*"],
"Rows": ["Auto", "*", "*"],
"Cells": [
{ "Row": 0, "Col": 0, "ColSpan": 3, "Cell.HeaderLink": "Plant Overview", "Content": { /* header card */ } },
{ "Row": 1, "Col": 0, "Cell.HeaderLink": "Production Rate", "Content": { /* gauge */ } },
{ "Row": 1, "Col": 1, "Cell.HeaderLink": "Active Alarms", "Content": { /* alarm viewer */ } },
{ "Row": 1, "Col": 2, "Cell.HeaderLink": "Shift Output", "Content": { /* KPI */ } }
]
}
}The Columns and Rows arrays define track sizes. Each entry can be:
"*" — equal share of remaining space (like CSS 1fr)"2*" — twice the share (like CSS 2fr)"Auto" — size to content"240" — fixed pixel width"*,min=200" — fractional with a minimum in pixelsStandard patterns:
| Layout | Columns | Rows |
|---|---|---|
| 3 equal columns, 2 rows | ["*","*","*"] | ["*","*"] |
| Header + 2 equal rows | ["*","*","*"] | ["Auto","*","*"] |
| Sidebar + main | ["240","*"] | ["*"] |
| Header + sidebar + main | ["240","*"] | ["Auto","*"] |
| 4 KPIs across top, trend below | ["*","*","*","*"] | ["Auto","*"] |
| Operator wall (4×3) | ["*","*","*","*"] | ["*","*","*"] |
In Canvas you place a gauge at Left: 472, Top: 320. In Dashboard you place a gauge at Row: 1, Col: 2. The engine handles pixel positioning, cell padding, and reflow.
This is a completely different mental model. If you find yourself calculating Left/Top/Width/Height for Dashboard elements, stop — you're building a Canvas display by accident.
Setting a row or column to "*" gives that track the space; it does not force the cell's content to fill it. A fixed-size gauge in a "*" row will sit at its native size inside a large cell, not stretch. For content that should fill the cell, use stretch-friendly controls (TrendChart, BarChart, AlarmViewer, DataGrid). Gauges are fixed size; place them in cells sized to match.
Not every element type works inside a Dashboard cell. Call list_elements('Dashboard') for the authoritative compatibility list in the current release. Rule of thumb:
Dynamics work in Dashboard for visual controls (FillColorDynamic on a TextBlock, VisibilityDynamic on a chart) but the animation dynamics (Rotate, Scale, MoveDrag, Skew, Bargraph) are Canvas-only — they're silently ignored in Dashboard cells.
A Dashboard grid already reflows: cells track their Columns/Rows sizing and re-pack on window resize. But a FrameworX solution is built from several displays that share one window — a Header, maybe a Footer, a Menu rail, and a content page docked into the middle. How each of those displays behaves when the window changes size is controlled by one display-level property, OnResize, plus a small set of per-element and per-display locks. Get these right and the whole layout breathes cleanly across a 4K control-room wall and a 1366-wide laptop; get them wrong and content compresses, clips, or floats.
OnResize decision treeSet OnResize once per display, by what the display is:
| Display kind | OnResize | Then also… |
|---|---|---|
| Dashboard / data page with a prominent element that should grow (DataGrid, TrendChart, AlarmViewer) | Responsive | Set the element locks IsWidthAlign + IsHeightAlign on that prominent element (see below). A full-width band element gets IsWidthAlign only; a bottom-pinned input row gets IsTopAlign + IsWidthAlign; a right-edge control gets IsLeftAlign; small top-left labels and nav icons get no locks. |
| Process diagram / drawing (P&ID, equipment layout) | StretchUniform | Nothing — the whole drawing scales as one, preserving aspect ratio. |
| Viewer / text page (text-led page where everything should scale together) | ResizeChildren | Nothing — children scale with the container. |
| Header / Footer band | Responsive | Set the display lock LockedHeight to pin the band to its native pixel height. Match the Header's native Width to the Layout Width so it does not compress horizontally. |
| Menu / SubMenu rail | Responsive | Set the display lock LockedWidth to pin the rail to its native pixel width. |
| Popup / Dialog / Form | NoAction | Nothing — the modal keeps its authored size. |
Docked Header / Footer / Menu are Responsive, not NoAction. The intuition that a fixed band should be "frozen" (NoAction) is wrong for a docked region: NoAction stops the band participating in the layout at all, while the demo-proven pattern is Responsive plus the matching dimension lock — LockedHeight for a Header/Footer, LockedWidth for a Menu. That keeps the band's pinned dimension fixed while the free dimension tracks the window. (NoAction is still correct for a Popup/Dialog/Form, which is not docked.)
Two different knobs — do not conflate them. Setting the Header region to span the full width of the layout (the region's HorizontalAlign = Stretch) is the layout-docking knob. It is not the same as OnResize = StretchUniform. One controls how the region docks into the layout; the other controls how the display's contents behave on resize.
The locks come in two levels. You author them as flat properties — on the element, or on the display — and the platform translates them into the underlying resize behavior. You never write the raw WPF attached-property XAML; just set the flat boolean.
Element-level locks (4) — set on an individual element inside a Responsive display. They are only honored when the display's OnResize is Responsive; on any other OnResize they are ignored.
| Property | Effect on resize |
|---|---|
IsWidthAlign | Stretch the element's width with the container. |
IsHeightAlign | Stretch the element's height with the container. |
IsLeftAlign | Move the element to track the container's right edge (keeps its right-side gap constant). |
IsTopAlign | Move the element to track the container's bottom edge (keeps its bottom gap constant). |
So IsWidthAlign/IsHeightAlign grow the element; IsLeftAlign/IsTopAlign reposition it. A DataGrid or TrendChart that should fill its area gets both IsWidthAlign + IsHeightAlign. A toolbar pinned to the bottom gets IsTopAlign + IsWidthAlign (it rides the bottom edge and stretches across). A small label in the top-left corner gets no locks — it stays put at its native size.
Display-level locks (2) — set on the display itself, to pin a docked region to native pixels under Responsive:
| Property | Use on | Effect |
|---|---|---|
LockedHeight | A docked Header or Footer band | Pins the band's height to its native pixels; the width still tracks the window. |
LockedWidth | A docked Menu or SubMenu rail | Pins the rail's width to its native pixels; the height still tracks the window. |
The shipped Asset Monitor demo is the canonical reference for every case above:
| Display | Native size | OnResize + locks |
|---|---|---|
| Header | 1546×60 | Responsive + LockedHeight; native Width matched to the layout Width (1546) so there is no horizontal compression. |
| HeaderPad | 1366×40 | Responsive + LockedHeight. |
| HeaderMobile | 400×40 | NoAction + LockedWidth + LockedHeight (a fixed-size mobile band). |
| MenuTree | 180×628 | Responsive + LockedWidth. The AssetsTree inside carries IsWidthAlign + IsHeightAlign; the three bottom TextBoxes carry IsTopAlign + IsWidthAlign. |
| Area (a Responsive Canvas) | — | Responsive; the DataGrid carries IsWidthAlign + IsHeightAlign; a FlowPanel carries IsWidthAlign; the top-left label TextBoxes carry no locks. |
| Home / OEEDashboard (Responsive Dashboards) | — | Responsive with Star-sized grid columns + a GridSplitter + two ChildDisplays. No element locks — the grid does the reflow. |
| OEE_Left / OEE_Right | — | StretchUniform (fixed-aspect card panels living inside the dashboard cells). |
| Site detail pages (Dallas, Detroit, Houston, Europe) | — | ResizeChildren. |
Notice the pattern in the two Responsive Dashboards (Home, OEEDashboard): when the grid itself carries the reflow — Star-sized columns, a splitter, ChildDisplays — the cells need no element locks at all. Element locks are for a Responsive display whose content is positioned rather than grid-tracked (the "Responsive Canvas" case, like Area above).
The landing page of a solution is, by convention, a Dashboard named Home that hosts two ChildDisplays in a responsive grid — one for navigation/network, one for features/KPIs — separated by a GridSplitter. In the demo, Home embeds Home_Network and Home_Features. This is the highest-leverage screen to get right: it is the operator's first impression and the preview customers see. Build it as a Responsive Dashboard with Star columns, a GridSplitter, and two ChildDisplay cells — no element locks needed.
Keep MainPage in place — never rename to "consolidate." The landing page in this pattern is named Home; the template's MainPage (Display ID 0) is a separate, reserved page — the Solution Center preview anchor. Build Home, point the Startup layout's Content region at it, and leave MainPage in place (a static placard is enough for the thumbnail). Do not rename MainPage out of the way, or rename Home onto it: renaming the ID-0 page builds green but silently detaches the preview anchor. An orphaned-looking MainPage beside a wired Home is the intended state — not a cleanup target. See Displays List Reference § Special Pages.
When a content page must also render well on a phone, do not try to make one Canvas reflow to both form factors. Split it into two child displays, each its own Canvas — one composed for the wide desktop layout, one for the narrow mobile layout — and select between them per client. (The demo's HeaderMobile band, sized 400×40 with NoAction + both display locks, is the header half of this same mobile-split idea.)
Six data cards in a 3-column × 2-row grid:
{ "Name": "PlantKPIs", "PanelType": "Dashboard", "DashboardDisplay": { "Columns": ["*", "*", "*"], "Rows": ["*", "*"], "Cells": [ { "Row": 0, "Col": 0, "Cell.HeaderLink": "Production Rate", "Content": { "Type": "CenterValue", "LinkedValue": "@Tag.Plant/ProductionRate", "CenterTextFormat": "N1", "AccentTextLink": "units/hr" } }, { "Row": 0, "Col": 1, "Cell.HeaderLink": "Active Alarms", "Content": { "Type": "CenterValue", "LinkedValue": "@Tag.Plant/AlarmCount", "CenterTextFormat": "N0", "AccentTextLink": "alarms" } }, { "Row": 0, "Col": 2, "Cell.HeaderLink": "Operator on Duty", "Content": { "Type": "TextBlock", "LinkedValue": "{@Tag.Shift/CurrentOperator}", "FontSize": 22, "FontWeight": "Bold" } }, { "Row": 1, "Col": 0, "Cell.HeaderLink": "Temp Trend", "Content": { "Type": "TrendChart", "Duration": "5m", "Pens": [{"Type":"TrendPen","LinkedValue":"@Tag.Plant/AvgTemp","Stroke":"#FFEF4444"}] } }, { "Row": 1, "Col": 1, "Cell.HeaderLink": "Pressure Trend", "Content": { "Type": "TrendChart", "Duration": "5m", "Pens": [{"Type":"TrendPen","LinkedValue":"@Tag.Plant/AvgPressure","Stroke":"#FF38BDF8"}] } }, { "Row": 1, "Col": 2, "Cell.HeaderLink": "Shift Output", "Content": { "Type": "BarChart", "LinkedValue": "@Tag.Shift/OutputByHour" } } ] } }Twelve cells. Full-screen control-room overview with one card per reactor / line / zone:
"Columns": ["*","*","*","*"], "Rows": ["*","*","*"]Asset tree on the left, detail panel on the right:
{ "DashboardDisplay": { "Columns": ["240", "*"], "Rows": ["Auto", "*"], "Cells": [ { "Row": 0, "Col": 0, "ColSpan": 2, "Cell.HeaderLink": "Production Area A", "Content": { "Type": "TextBlock", "LinkedValue": "{@Tag.Site/Name} — {@Server.DateTimeInfo.Now}" } }, { "Row": 1, "Col": 0, "Cell.HeaderLink": "Equipment", "Content": { "Type": "AssetsTree" } }, { "Row": 1, "Col": 1, "Cell.HeaderLink": "{@Client.Context.AssetName}", "Content": { "Type": "ChildDisplay", "DisplayLink": "EquipmentDetail" } } ] } }The AssetsTree has all its bindings pre-wired to @Client.Context.* by default — drop it in and navigation "just works."
{ "Row": 0, "Col": 0, "ColSpan": 2, ... } // cell spans columns 0 and 1 { "Row": 1, "Col": 0, "RowSpan": 2, ... } // cell spans rows 1 and 2Use ColSpan on a header card to stretch it across all grid columns. Use RowSpan when you want a tall element (AlarmViewer, AssetsTree) next to shorter cards.
| Cell purpose | Best control | Why |
|---|---|---|
| Display title / section header | TextBlock with composite LinkedValue | "{@Tag.Site/Name} — {@Server.DateTimeInfo.Now}" in one element |
| Single-value KPI (numeric) | CenterValue | Pre-styled big-number-plus-unit tile |
| Single-value KPI (string) | TextBlock with FontSize 24+ | Simpler than CenterValue for strings |
| Time-series trend | TrendChart | The workhorse |
| Tag value dial | RadialGauge | Gauge with threshold bands |
| Tag value bar (linear) | LinearGauge | For bar-style KPIs with setpoint pointer |
| Cumulative count / meter | DigitalGauge or DigitalMeter | Specialty numeric readouts |
| Categorical comparison | BarChart | e.g., output by shift |
| Current alarms | AlarmViewer | Pre-wired to Client.AlarmPage context |
| Asset hierarchy navigation | AssetsTree | Pre-wired to Client.Context |
| Dropdown selector | ComboBox (DataTable-backed for FK) | Zero-script FK lookup |
| Data table / list | DataGrid | The list in list→detail |
| Document viewer (SOP, work order) | PdfViewer | URL-bound inline PDF |
| Fleet/plant map | MapsOSM | Lat/long-positioned markers |
| Embedded another display | ChildDisplay | Reusable detail panels |
| Multiple panels user switches | TabControl | Manual click-to-switch |
| Slideshow of status boards | Carousel | Auto-cycle with AutoCycleLink |
| Collapsible panel | Expander | Click to expand advanced settings |
| Card-per-item layout | FlowPanel | N items from a data source, one template |
Cell.HeaderLink patternEvery cell should have a Cell.HeaderLink. The value is either:
"Production Rate""@Tag.CurrentAsset/Name""Reactor R-101: {@Tag.R101/Status}"The header renders as a small title strip at the top of the card, in the theme's card-header style. Leaving it empty gives you a headerless card — useful for the header / status row banding the top of the display, but unusual elsewhere.
Most dashboard cells end up being trend charts. The canonical setup:
{ "Type": "TrendChart", "Duration": "5m", "YMinValue": 0, "YMaxValue": 100, "YLabels": 5, "XGridLines": 6, "YGridLines": 5, "LegendPlacement": "BottomPanel", "VerticalCursor": true, "BackgroundTheme": "ControlBackground", "ForegroundTheme": "TextForeground", "BorderBrushTheme": "DefaultBorder", "Pens": [ { "Type": "TrendPen", "LinkedValue": "@Tag.Reactor/Temperature_C", "PenLabel": "Temperature", "Stroke": "#FFEF4444", "StrokeThickness": 2 }, { "Type": "TrendPen", "LinkedValue": "@Tag.Reactor/Setpoint", "PenLabel": "Setpoint", "Stroke": "#FF34D399", "StrokeThickness": 1 } ] }"Pens": [ {...}, {...} ] ← prefer this for readability"Pens": { "Type": "TrendPenList", "Children": [ {...} ] } ← older form, also accepted| Property | Required | Notes |
|---|---|---|
LinkedValue | ? | Tag binding: @Tag.Reactor/Temperature_C |
PenLabel | — | Legend text |
Stroke | — | Line color hex. Not theme-aware — hex only. |
StrokeThickness | — | Default 1; use 2 for emphasis, 3 for setpoint/limit |
YMin / YMax | — | Per-pen Y scale (overrides chart scale) |
YAxisPosition | — | "Left" (default) or "Right" for dual-axis plots |
Auto | — | true for auto-scaling that pen |
Visible | — | true/false |
| Duration | When |
|---|---|
"1m" | Demos — populates visibly in ~60s |
"5m" | Default operator view — recent activity |
"15m" | Short-term process monitoring |
"1h" / "4h" | Shift-length trends |
"24h" / "7d" | Production reports, historical review |
"BottomPanel" (default), "RightPanel", "TopPanel", "None". For narrow cells use "RightPanel". For wide cells "BottomPanel".
Call list_elements('Charts') for the authoritative chart catalog in the current release. TrendChart is the right default for time-series data. For X-vs-Y scatter plots or correlation displays, verify the current element set before committing — the available chart types and their schemas evolve between releases.
Use a UserType-typed Client tag as the "selected row" carrier. The DataGrid pushes selected-row values into its fields, detail controls read from its fields via @Tag.Selected<X>.Field. Zero code-behind.
@Tag.SelectedReactor with UserType: "ReactorRow".SelectedValuesLink to "@Tag.SelectedReactor". The DataGrid automatically pushes values from the currently-selected row into each matching field of the UDT.@Tag.SelectedReactor.Name, @Tag.SelectedReactor.Temperature, etc. They update automatically as the operator clicks rows.{ "Type": "DataGrid", "ItemsSource": "@Dataset.Query.ActiveReactors", "SelectedValuesLink": "@Tag.SelectedReactor", "Columns": { "Type": "GridColumnList", "Children": [ { "Type": "GridColumn", "Title": "Reactor", "FieldName": "Name", "Width": 120 }, { "Type": "GridColumn", "Title": "Temp (°C)", "FieldName": "Temperature", "Width": 100 }, { "Type": "GridColumn", "Title": "Pressure", "FieldName": "Pressure", "Width": 100 }, { "Type": "GridColumn", "Title": "Status", "FieldName": "Status", "Width": 100 } ] }, "BackgroundTheme": "ControlBackground", "ForegroundTheme": "TextForeground", "BorderBrushTheme": "DefaultBorder" }{
"Row": 1, "Col": 1, "Cell.HeaderLink": "Temperature",
"Content": {
"Type": "CenterValue",
"LinkedValue": "@Tag.SelectedReactor.Temperature",
"CenterTextFormat": "N1",
"AccentTextLink": "°C"
}
},
{
"Row": 1, "Col": 2, "Cell.HeaderLink": "Pressure",
"Content": {
"Type": "CenterValue",
"LinkedValue": "@Tag.SelectedReactor.Pressure",
"CenterTextFormat": "N1",
"AccentTextLink": "bar"
}
},
{
"Row": 2, "Col": 1, "ColSpan": 2, "Cell.HeaderLink": "Status",
"Content": {
"Type": "TextBlock",
"LinkedValue": "Status: {@Tag.SelectedReactor.Status}",
"FontSize": 16
}
}When the operator clicks a row in the DataGrid, all three detail cells update simultaneously. No script, no event handler.
FieldNames (case-sensitive).{
"Type": "ComboBox",
"ItemsSourceType": "DataTable",
"ItemsSourceLink": "@Dataset.Query.OperatorsList",
"DisplayMember": "FullName",
"SelectedValuePath": "OperatorID",
"SelectedValueLink": "@Tag.Shift/CurrentOperatorId",
"Foreground": "theme:TextForeground",
"Background": "theme:ControlBackground",
"BorderBrush": "theme:DefaultBorder"
}When the operator picks "Maria Costa" from the dropdown, the OperatorID (say 42) lands in @Tag.Shift/CurrentOperatorId automatically. Other displays binding to that tag update immediately.
Use this for: operator selection, product changeover, reactor mode select, batch selection — anywhere the user picks one row from a database-backed list.
"DataTable" — the pattern above, dataset query as source"Array" — bound to an array tag"StringTag" — comma-separated string (legacy, avoid)"Text" — hardcoded comma-separated inline optionsThe AlarmViewer default template ships pre-wired to @Client.AlarmPage.* context tags:
{ "Type": "AlarmViewer", "ShowRowSelectorPane": false, "BackgroundTheme": "ControlBackground", "ForegroundTheme": "TextForeground" }That's the entire cell content. All alarms, all columns, all features — wired.
{ "Type": "AlarmViewer", "Filter": "Area = 'ReactorZone'", "ShowRowSelectorPane": false }Filter syntax: "Priority >= 2", "Area = 'Tank1'", or a tag binding "@Tag.AlarmFilter".
"Columns": { "Type": "GridColumnList", "Children": [ { "Type": "GridColumn", "Title": "Active", "FieldName": "ActiveTime_Ticks", "Width": 140 }, { "Type": "GridColumn", "Title": "Tag", "FieldName": "TagName", "Width": 200 }, { "Type": "GridColumn", "Title": "Msg", "FieldName": "Message", "Width": 400 }, { "Type": "GridColumn", "Title": "Pri", "FieldName": "Priority", "Width": 50 } ] }Available field names: AckStatus, ActiveTime_Ticks, TagName, Group, Value, ID, ItemName, State, AckRequired, Condition, SolutionName, Area, Priority, NormTime_Ticks, AckTime_Ticks, UserName, Message, Duration, Category, DateCreated_Ticks, AuxValue, AlarmLimit, PreviousValue, AuxValue2, AuxValue3. Tick fields format as DateTime at render time.
The canonical asset-driven master-detail pattern. One "detail template" display shows whatever asset the operator picks in the tree.
{ "Type": "AssetsTree" }The default template already binds:
LinkedValue → @Client.Context.AssetName (output — which asset is selected)AssetPathLink → @Client.Context.AssetPath (output — full path){ "Type": "ChildDisplay", "DisplayLink": "EquipmentDetailTemplate" }Inside EquipmentDetailTemplate, every binding uses Asset(@Client.Context.AssetPath + ".Property") or direct @Tag paths constructed from the context. When the operator clicks a different tree node, the ChildDisplay re-renders with the new asset's data.
{ "Type": "ChildDisplay", "DisplayLink": "@Tag.DetailDisplayName" }A Script calculates which detail display to show based on the selected asset's type (Pump → PumpDetail, Reactor → ReactorDetail) and writes to @Tag.DetailDisplayName. The ChildDisplay swaps automatically.
Both accept the same structure: HeaderElements (navigation chrome) and TabItems (panels). Difference:
AutoCycleLink: 5 for 5-second auto-cycling. Lobby displays, rotating KPI boards.{
"Type": "Carousel",
"AutoCycleLink": 5,
"TabItems": [
{
"Type": "TabItem",
"IsSelected": true,
"Header": { "Type": "TextBlock", "LinkedValue": "Production" },
"Children": [ { "Type": "TrendChart", ... } ]
},
{
"Type": "TabItem",
"Header": { "Type": "TextBlock", "LinkedValue": "Quality" },
"Children": [ { "Type": "BarChart", ... } ]
},
{
"Type": "TabItem",
"Header": { "Type": "TextBlock", "LinkedValue": "Alarms" },
"Children": [ { "Type": "AlarmViewer" } ]
}
]
}Rules:
IsSelected: trueChildren is an array — can contain multiple elements per tabAutoCycleLink can be a number (seconds) OR a tag binding ("@Tag.ShowroomCycleSeconds") for runtime-configurable cycling{ "Type": "CenterValue", "LinkedValue": "@Tag.Plant/ProductionRate", "CenterTextFormat": "N1", "AccentTextLink": "units/hr", "CenterFontSize": 48, "AccentFontSize": 14, "BackgroundTheme": "ControlBackground" }CenterTextFormat: "N0" (integer), "N1" (1 decimal), "N2" (2 decimals), "P1" (percent 1 decimal). AccentTextLink is the unit or caption under/beside the main number.
{ "Type": "TextBlock", "LinkedValue": "Throughput: {@Tag.Plant/ProductionRate} units/hr ({@Tag.Plant/TargetPct}% of target)", "FontSize": 16, "FontWeight": "SemiBold", "ForegroundTheme": "TextForeground" }{ "Type": "TextBlock", "LinkedValue": "{@Tag.Plant/AvgTemp} °C", "FontSize": 32, "Dynamics": [ { "Type": "TextColorDynamic", "LinkedValue": "@Tag.Plant/AvgTemp", "ChangeColorItems": [ { "Type": "ChangeColorItem", "ChangeLimit": 0, "LimitColor": "#FF38BDF8" }, { "Type": "ChangeColorItem", "ChangeLimit": 75, "LimitColor": "#FF34D399" }, { "Type": "ChangeColorItem", "ChangeLimit": 90, "LimitColor": "#FFF59E0B" }, { "Type": "ChangeColorItem", "ChangeLimit": 100, "LimitColor": "#FFEF4444" } ] } ] }Blue cold → green normal → amber warning → red alarm.
Same rule as Canvas: page-to-page navigation belongs in the Header display, not on content pages. Content pages get only in-page interactions.
{ "Name": "Header", "PanelType": "Dashboard", "DashboardDisplay": { "Columns": ["Auto","Auto","Auto","Auto","*","Auto"], "Rows": ["*"], "Cells": [ { "Row": 0, "Col": 0, "Content": { "Type": "Button", "LabelLink": "Overview", "Dynamics": [{"Type":"ActionDynamic","MouseLeftButtonDown":{"Type":"DynamicActionInfo","ActionType":"OpenDisplay","ObjectLink":"OperationsOverview"}}] } }, { "Row": 0, "Col": 1, "Content": { "Type": "Button", "LabelLink": "Alarms", ... } }, { "Row": 0, "Col": 2, "Content": { "Type": "Button", "LabelLink": "Trends", ... } }, { "Row": 0, "Col": 3, "Content": { "Type": "Button", "LabelLink": "Reports", ... } }, { "Row": 0, "Col": 5, "Content": { "Type": "TextBlock", "LinkedValue": "Logged in: {@Client.Username}" } } ] } }Minimum button size: 100×32. Recommended: 130×40 for touch-friendly control rooms.
For DataGrids, a double-click to drill into detail:
"Dynamics": [ { "Type": "ActionDynamic", "MouseDoubleClick": { "Type": "DynamicActionInfo", "ActionType": "OpenDisplay", "ObjectLink": "ReactorDetail" } } ]The target display reads @Tag.SelectedReactor.Name (etc.) — so you get "double-click row → open detail view of that row" with zero code.
RotateDynamic, ScaleDynamic, MoveDragDynamic, SkewDynamic, BargraphDynamic. If you need a rotating element or a custom level-bar, move that cell's content to a Canvas display embedded via ChildDisplay, or pick a control with the behavior built in (LinearGauge for level, symbols for motor-running-spin).Cell.HeaderLink renders in a theme-defined style — you can't set FontSize or Foreground on the header itself from the cell. If you need a custom header, set Cell.HeaderLink to empty string and put a TextBlock as the first element inside the cell Content.@Tag.SelectedValueLink with a pre-populated default.PanelType: "Dashboard" is setOnResize is set by display kind: Responsive for a data page whose prominent element should grow; StretchUniform for a process diagram/drawing; ResizeChildren for a viewer/text page; Responsive + LockedHeight for a docked Header/Footer (native Width matched to the Layout Width); Responsive + LockedWidth for a docked Menu/SubMenu rail; NoAction for a Popup/Dialog/Form (docked Header/Footer/Menu are NOT NoAction)Responsive display with positioned (non-grid) content, the prominent element carries the right element locks — IsWidthAlign/IsHeightAlign to stretch, IsLeftAlign/IsTopAlign to track the right/bottom edge; small top-left labels and nav icons carry none. A grid-driven Responsive Dashboard (Star columns + GridSplitter) needs no element locksResponsive Dashboard hosting two ChildDisplays (Star columns + GridSplitter)DashboardDisplay object includes Columns, Rows, CellsRow and Col; Cell.HeaderLink is either a non-empty string or absentDisplayMember AND SelectedValuePath AND SelectedValueLinkLinkedValue + Strokeget_state after write shows errorList emptyget_display_tree(element=<DisplayName>) returns — for each navigation Button or other control carrying a LabelLink, labelResolved matches the authored intent (no default caption left in place, no unexpected empty text)Cell.HeaderLink was authored, the resolved header text matches intent (the documented empty-string case for the headerless-card pattern is fine; the bug is the unintentionally-empty case)TextBlock // headers, composite KPIs, status text CenterValue // big-number KPI tiles TrendChart // all time-series (the workhorse) BarChart // categorical comparison AlarmViewer // alarm list with default template AssetsTree // plant navigation sidebar ChildDisplay // embedded detail panel DataGrid // list in list-to-detail ComboBox // FK selector dropdown RadialGauge // circular gauge cells{
"Name": "MyDashboard",
"PanelType": "Dashboard",
"DashboardDisplay": {
"Columns": ["*", "*", "*"],
"Rows": ["Auto", "*"],
"Cells": [
{ "Row": 0, "Col": 0, "ColSpan": 3, "Cell.HeaderLink": "Header", "Content": { } },
{ "Row": 1, "Col": 0, "Cell.HeaderLink": "Card 1", "Content": { } },
{ "Row": 1, "Col": 1, "Cell.HeaderLink": "Card 2", "Content": { } },
{ "Row": 1, "Col": 2, "Cell.HeaderLink": "Card 3", "Content": { } }
]
}
}The minimal structural skeleton an AI session can paste-and-fill. Replace the empty Content: { } objects with the controls from Section 3 (TextBlock, CenterValue, TrendChart, AlarmViewer, AssetsTree, DataGrid, ComboBox, RadialGauge, ChildDisplay, BarChart). The header row spans all three columns; the body row gives equal width to three cards. Add more rows or vary track sizes via the patterns in §1.