Alarm Items (Reference) define individual tags or expressions monitored for alarm conditions within your FrameworX solution. Alarm Items are the fundamental alarm objects that:
Each Alarm Item represents a single monitored condition that generates alarms based on your defined thresholds and settings.
Two Alarm Items on the same tag and condition are not supported, because the tag keeps one link per condition: both rows raise alarms, but Tag.<name>.<Condition> and the saved limits follow only one of them.
| Property | Description | Required |
|---|---|---|
| TagName | The tag being monitored for alarm events | Yes |
| Condition | Trigger condition (Hi, Lo, RateOfChange, etc.) | Yes |
| Limit | Primary threshold value | Yes |
| Limit1 | Secondary threshold (for shift-based limits) | No |
| Limit2 | Tertiary threshold (for shift-based limits) | No |
| Group | Associated AlarmGroup for shared properties | Yes |
| Area | AlarmArea for hierarchical organization | No |
| Priority | Alarm priority level | No |
| Message | Text displayed when alarm triggers | No |
| Disable | Enable/disable the alarm | No |
| Deadband | Range where changes are ignored | No |
| Setpoint | Target value for deviation alarms | No |
| SetpointDeadband | Range around setpoint to ignore | No |
| AuxValue | Additional information field | No |
| AuxValue2 | Secondary auxiliary value | No |
| AuxValue3 | Tertiary auxiliary value | No |
| Comment | Notes about the alarm item | No |
| Condition | Description | Formula |
|---|---|---|
| Hi | High alarm | Tag ≥ Limit |
| HiHi | High-high alarm (auto-acks Hi) | Tag ≥ Limit |
| Lo | Low alarm | Tag ≤ Limit |
| LoLo | Low-low alarm (auto-acks Lo) | Tag ≤ Limit |
| RateOfChange | Rate exceeds limit | ΔTag/Δt ≥ Limit (s) |
| DeviationMinor | Minor deviation from setpoint | |Tag - Setpoint| > Limit |
| DeviationMajor | Major deviation from setpoint | |Tag - Setpoint| > Limit |
| Equal | Exact match | Tag = Limit |
| GreaterThan | Greater than | Tag > Limit |
| GreaterEqual | Greater or equal | Tag ≥ Limit |
| LessThan | Less than | Tag < Limit |
| LessEqual | Less or equal | Tag ≤ Limit |
| Changed | Any change | Tag value changed |
| ChangedUp | Value increased | Tag value increased |
| ChangedDown | Value decreased | Tag value decreased |
| NotEqual | Not equal | Tag ≠ Limit |
Alarms will be generated even when the quality differs from 192 (good). |
Example configuration:
TagName: Tank1.Temperature
Condition: HiHi
Limit: 95
Group: Critical
Message: "Tank 1 Critical Temperature"
Priority: 100Use multiple limit values for different operational periods:
| Property | Usage |
|---|---|
| Limit | Default/primary threshold |
| Limit1 | Secondary threshold (e.g., day shift) |
| Limit2 | Tertiary threshold (e.g., night shift) |
Enable via Alarms → Global Settings → Enable LimitsByShift
Prevents alarm chattering:
Value Deadband:
Setpoint Deadband:
Access alarm item state at runtime via @Alarm.Item.[ItemName]:
// Check alarm state bool active = @Alarm.Item.HighTemp.Alarm == 1; DateTime activeTime = @Alarm.Item.HighTemp.ActiveTime; // Get current values string currentValue = @Alarm.Item.HighTemp.LastValue; double limitValue = @Alarm.Item.HighTemp.Limit; |
Alarm not triggering:
Excessive alarms:
Wrong threshold: