Devices Nodes (Reference) represent physical devices or PLCs in the communication network, with each node containing one or more communication points mapped to device addresses.
Device Nodes provide:
Each node maps to a specific device (PLC, RTU, controller) accessible through its parent channel.
The columns below are the user-editable properties of a node. Additional columns appear in the grid but are written by the platform itself — see Platform-managed columns immediately below for those.
| Property | Description | Required |
|---|---|---|
| Name | Plain identifier for the node (e.g., DeltaV_Server). The parent channel relationship lives in the Channel column; do NOT encode the channel in the Name with dot-notation. | Yes |
| Channel | Name of the parent DevicesChannels row. | Yes |
| PrimaryStation | Primary device address. Protocol-dependent format — consult the protocol reference for the exact syntax. | Yes |
| BackupStation | Optional backup device address. Protocol-dependent format. | No |
| Description | Free-text documentation for this node. | No |
| Category | Editable classification label you assign to organize and tag nodes by category — the same classification field available on Device Channels and Device Access Types. Categories assigned to a node help filter and organize nodes, for example in the Device module diagnostics views and in Historian and Dataset data views. | No |
The columns below appear on the Devices → Nodes grid but are written by the platform itself. They are NOT for hand-editing, scripted edits, or AI edits — treat them as read-only diagnostic surface. The Tags Import tool writes the Sync* columns; the platform owns the rest.
| Column | Meaning | Written by |
|---|---|---|
| SyncDate | Timestamp of the last node-configuration import or synchronization | Tags Import tool |
| SyncStation | Source details of the last import | Tags Import tool |
| SyncSettings | Configuration of the last import | Tags Import tool |
| ID | Internal row identifier | Platform |
| VersionID | Internal version marker | Platform |
| LockState | Internal edit-lock state | Platform |
| LockOwner | Internal lock owner | Platform |
| DateCreated | Internal creation timestamp | Platform |
| DateModified | Internal modification timestamp | Platform |
Protocol-specific addressing:
To add redundancy to a specific node, enable the Backup Station column. If the column is not visible, right-click any column header and select it to enable. The configuration is the same as for PrimaryStation, if the primary connection fails, the system will attempt the backup station. If the backup station also fails, the system will automatically switch back to the primary, and so on. The failover timeout can be configured in Devices / Channels / Timeout.
The following properties can be accessed from anywhere in the software:
Toggle this property between true and false to force a switch between the PrimaryStation and BackupStation:@Device.Node.<NodeName>.ForceSwitch = true;
Toggle this property between true and false to enable or disable automatic switching when the current node encounters an error:@Device.Node.<NodeName>.DisableAutoSwitch = true;
Use this property to verify whether the primary or backup station is currently active:@Device.Node.<NodeName>.IsPrimary = true;
This property is true while the node communicates with the BackupStation:@Device.Node.<NodeName>.IsBackup
From FrameworX 10.1.6, this property has its own identifier. It is reserved for three-station failover and reads false in current configurations:@Device.Node.<NodeName>.IsFailOver
In 10.1.5, IsFailOver and IsBackup shared one identifier, so a reference to IsFailOver returned the backup status. From 10.1.6, IsFailOver returns the failover flag, which reads false. Use IsBackup to read the backup status, and review scripts, display bindings and reports reading either property. |
You can view additional properties available for each node by typing |
| Source | Description | Supported Protocols |
|---|---|---|
| PLC Programs | Import from PLC files | ControlLogix, Siemens |
| OPC Browse | Discover OPC servers | OPC UA |
| Online Discovery | Scan network devices | Modbus, BACnet |
| CSV Import | Bulk configuration | All protocols |
See → Importing PLC Addresses for detailed instructions
Channel
--- Node (Device)
--- Point 1
--- Point 2
Channel: ModbusTCP_Main
Name: PLC_Tank_Farm
PrimaryStation: 192.168.1.100:502
BackupStation: 192.168.1.101:502
Description: Tank farm controllerChannel: EthernetIP_Channel
Name: CLX_Line1
PrimaryStation: 192.168.1.50;1;0
Description: Line 1 ControlLogixChannel: OPCUA_Channel
Name: OPC_Server1
PrimaryStation: opc.tcp://server:4840
Description: Main OPC UA ServerThe SyncDate, SyncStation, and SyncSettings columns are read-only provenance written by the Tags Import tool when nodes are imported or re-synchronized. They are not user-editable — do not type into them and do not target them from scripts or AI tools.
Node offline:
Import failures:
Communication errors:
Points not updating:
Monitor node health:
// Node status bool isOnline = @Device.Node.NodeName.IsOnline; // Station active string activeStation = @Device.Node.NodeName.ActiveStation; // Communication stats int successCount = @Device.Node.NodeName.SuccessCount; int errorCount = @Device.Node.NodeName.ErrorCount; // Last sync DateTime syncTime = @Device.Node.NodeName.LastSync; |