This document has only the specific information about the device connection settings and its address syntax.
Refer to the User Guide for more information on the Device Module.
On this page:
ECOM Ethernet driver implements communication with Automation Direct (PLC Direct/Koyo) device. It operates as a Master on the TCP/IP network. The communications blocks are dynamically created according the pooling cycle defined on the AccessType for each Device Point.
Communication Driver Information | |
---|---|
Driver name | Ecom |
Assembly Name | T.ProtocolDriver.Ecom |
Assembly Version | 1.2.2.0 |
Available for Linux | False |
Devices supported | Automation Direct (PLC Direct/Koyo) |
Manufacturer | Koyo |
Protocol | Proprietary over TCP/IP |
PC Requirements | Standard PC Ethernet interface board |
Communication block size | User configurable; default is 255. |
Protocol Options | None |
Multi-threading | User configurable; default is one thread for each network node |
Max number of nodes | User defined |
Operand | Address Range | Read | Write | Data Type | Address size |
C Control Relays | 0–1777 | Yes | Yes | Bit | 1 bit |
CT Control Status | 0-177 | Yes | Yes | Bit | 1 bit |
SP Special Relays | 0-777 | Yes | Yes | Bit | 1 bit |
S Stages | 0-1777 | Yes | Yes | Bit | 1 bit |
T Timer Status | 0-377 | Yes | Yes | Bit | 1 bit |
Y Output Points | 0-777 | Yes | Yes | Bit | 1 bit |
X Input Points | 0-777 | Yes | - | Bit | 1 bit |
V Memory | 0-41237 | Yes | Yes | Word | 2 bytes |
Some devices work with word data using byte swap, so for those devices the option byte swap in Modifiers column in the Point table must be set. |
BlockSize: Defines the maximum amount of items per group, the default value is 255.
TCP/IP :
SlaveId: Set this field with the address of the slave device in the Network (PLC ID).
TCP/IP :
Where :
E.g.: 192.168.1.101 ; 28784; 1
The syntax for the ECOM communication points is: <Operand Type><Octal Address>
Where: <Operand Type> indicates the memory area :
For more information about the valid operands, refer to the Supported Operands aforementioned:
E.g.: V0 (Operand = Memory, Address = 0)
Ecom Revision History | |
---|---|
Version | Notes |
1.2.2.0 | Initial release on new documentation standards. |